EasyManua.ls Logo

Mitsubishi FX3U Series - FNC 63 - INCD Incremental Drum Sequencer

Mitsubishi FX3U Series
944 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
398
FX3G/FX3U/FX3GC/FX3UC Series
Programming Manual - Basic & Applied Instruction Edition
14 Handy Instruction – FNC 60 to FNC 69
14.4 FNC 63 – INCD / Incremental Drum Sequencer
14.4 FNC 63 – INCD / Incremental Drum Sequencer
Outline
This instruction creates many output patterns using a pair of counters.
1. Instruction format
2. Set data
3. Applicable devices
S1: "D.b" is available only in FX3U and FX3UC PLCs. However, index modifiers (V and Z) are not available.
S2: This function is supported only in FX3U/FX3UC PLCs.
Explanation of function and operation
1. 16-bit operation (INCD)
The current value of a counter is compared with the data table having "n" lines starting from (which
occupies "n" lines x 1 device). When is equivalent to the table data, the current output is reset, and the next
output is set to ON. In this way, the ON/OFF status of specified outputs is controlled in turn.
Operand type Description Data type
Head word device number storing the set value 16-bit binary
Head number of counters whose current value is monitored 16-bit binary
Head bit device number to be output Bit
n Number of output bit devices [1 n 64] 16-bit binary
Oper-
and
Type
Bit Devices Word Devices Others
System User Digit Specification System User
Special
Unit
Index
Con-
stant
Real
Number
Charac-
ter String
Pointer
XYMTCSD
.b KnX KnY KnM KnS T C D R
U\G
V Z Modify K H E "
"P
33333333S2 3
33
33 3 S1 3
n 33
FNC 63
INCD
Mnemonic Operation Condition
16-bit Instruction
9 steps INCD
Mnemonic Operation Condition
Continuous
Operation
32-bit Instruction
S
1
S
1
S
2
D
S
1
S
1
S
2
S
2
D
D
1
S
2
D
1
S
1
D
1
S
2
Command
input
FNC 63
INCD
nS
1
S
2
D
K9999
Count signal
S
2

Table of Contents

Other manuals for Mitsubishi FX3U Series

Related product manuals