Page #531 background image
529
FX3G/FX3U/FX3GC/FX3UC Series
Programming Manual - Basic & Applied Instruction Edition
19 Data Operation 2 – FNC140 to FNC149
19.3 FNC142 – BTOW / BYTE to WORD
11
FNC30-FNC39
Rotation and
Shift
12
FNC40-FNC49
Data Operation
13
FNC50-FNC59
High-Speed
Processing
14
FMC60-FNC69
Handy
Instruction
15
FNC70-FNC79
External FX I/O
Device
16
FNC80-FNC89
External FX
Device
17
FNC100-FNC109
Data
Transfer 2
18
FNC110-FNC139
Floating Point
19
FNC140-FNC149
Data
Operation 2
20
FNC150-FNC159
Positioning
Control
19.3 FNC142 – BTOW / BYTE to WORD
Outline
This instruction combines the low-order 8 bits (low-order byte) of consecutive 16-bit data.
1. Instruction format
2. Set data
3. Applicable devices
Explanation of function and operation
1. 16-bit operation (BTOW and BTOWP)
1) The low-order byte (8 bits) of "n" 16-bit data starting from is combined, and stored in "n/2" devices starting
from as shown below.
2) The high-order byte (8 bits) of each combination source 16-bit data ( and later) is ignored.
3) When "n" is an odd number, "00H" is stored in the high-order byte (8 bits) of the final one among the combination
result destination devices as shown below.
For example, when "n" is "5", the low-order byte (8 bits) of to +4 is stored in to +2, and
"00H" is stored in the high-order byte (8 bits) of +2.
4) When "n" is "0", the BTOW instruction is not executed.
Operand type Description Data type
Head device number storing data to be combined in byte units
16-bit binary
Head device number storing data acquired by combination in byte units
n Number of byte data to be combined (0 n)
Oper-
and
Type
Bit Devices Word Devices Others
System User Digit Specification System User
Special
Unit
Index
Con-
stant
Real
Number
Charac-
ter String
Pointer
XYMTCSD.b KnX KnY KnM KnS T C D R U\G VZModifyKH E ""P
3333 3
3333 3
n 33 33
P
FNC 142
BTOW
Mnemonic Operation Condition
16-bit Instruction
7 steps
BTOW
BTOWP
Mnemonic Operation Condition
Continuous
Operation
Pulse (Single)
Operation
32-bit Instruction
S
D
S
D
S
D
Command
input
FNC142
BTOWP
S
D
n
b15 b8 b7 b0
S
+0
+1
...
The high-order byte is ignored.
+2
+n-1
"n"
bytes
1st byte data
2nd byte data
3rd byte data
"n"th byte data
D
+0
+1
+n/2
*
...
2nd byte
4th byte
"n"th byte
1st byte
3rd byte
"n-1"th byte
...
...
b15 b8 b7 b0
* When "n" is an odd number,
refer to "3)" below
S
S
S
D
D
D
00H
b15 b8 b7 b0
S
+0
+1
The high-order bytes is ignored.
+2
When
"n" is
"5"
D
+0
+1
+2
34H
78H
12H
56H
9AH
ABH
CDH
ABH
12H
34H
78H
EFH 56H
CDH
9AH
+3
+4
When "n" is "5",
"00H" is stored.
b15 b8 b7 b0

Table of Contents

Other manuals for Mitsubishi FX3U Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi FX3U Series and is the answer not in the manual?

Mitsubishi FX3U Series Specifications

General IconGeneral
BrandMitsubishi
ModelFX3U Series
CategoryController
LanguageEnglish

Related product manuals