577
FX3G/FX3U/FX3GC/FX3UC Series
Programming Manual - Basic & Applied Instruction Edition
22 External Device – FNC170 to FNC179
22.4 FNC177 – WR3A / Write to Dedicated Analog Block
21
FNC160-FNC169
Real Time Clock
Control
22
FNC170-FNC179
External Device
23
FNC180
Alternate
Instructions
24
FNC181-FNC189
Others
25
FNC190-FNC199
Block Data
Operation
26
FNC200-FNC209
Character String
Control
27
FNC210-FNC219
Data
Operation 3
28
FNC220-FNC249
Data
Comparison
29
FNC250-FNC269
Data Table
Operation
30
FNC270-FNC275
Ex-Device
Inverter Comms
22.4 FNC177 – WR3A / Write to Dedicated Analog Block
Outline
This instruction writes a digital value to the analog block FX0N-3A
*1
or FX2N-2DA.
1. Instruction format
2. Set data
3. Applicable devices
Explanation of function and operation
1. 16-bit operation (WR3A)
m1 : Special block number
FX3G/FX3U/FX3GC/FX3UC (D, DS, DSS) PLCs : K0 to K7
FX3UC-32MT-LT(-2) : K1 to K7 (K0 indicates the built-in CC-Link/LT master.)
m2 : Analog output channel number
FX0N-3A
*1
: K1 (ch 1)
FX2N-2DA : K21 (ch 1) or K22 (ch 2)
: Data to be written
Specify a value output to the analog block.
FX
0N-3A
*1
: 0 to 255 (8 bits)
FX2N-2DA : 0 to 4095 (12 bits)
*1. The FX0N-3A is available only for the FX3U and FX3UC PLCs.
Operand Type Description Data Type
m1
Special block number
-FX3G/FX3U/FX3GC/FX3UC (D, DS, DSS) PLCs: K0 to K7
-FX3UC-32MT-LT(-2) : K1 to K7
16-bit binary
m2 Analog output channel number 16-bit binary
Data to be written or word device storing data to be written 16-bit binary
Oper-
and
Type
Bit Devices Word Devices Others
System User Digit Specification System User
Special
Unit
Index
Con-
stant
Real
Number
Charac-
ter String
Pointer
XYMTCSD
.b KnX KnY KnM KnS T C D R
U\G
V Z Modify K H E "
"P
m1 33333333 33333
m2 33333333 33333
3333333 333
P
FNC 177
WR3A
Mnemonic Operation Condition
16-bit Instruction
7 steps
WR3A
WR3AP
Mnemonic Operation Condition
Continuous
Operation
Pulse (Single)
Operation
32-bit Instruction
S
S
FNC177
WR3A
m1
m2
Command
input
S
S

Table of Contents

Other manuals for Mitsubishi FX3U Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi FX3U Series and is the answer not in the manual?

Mitsubishi FX3U Series Specifications

General IconGeneral
BrandMitsubishi
ModelFX3U Series
CategoryController
LanguageEnglish

Related product manuals