468
FX3G/FX3U/FX3GC/FX3UC Series
Programming Manual - Basic & Applied Instruction Edition
16 External FX Device – FNC 80 to FNC 89
16.8 FNC 87 – RS2 / Serial Communication 2
Cautions
For other cautions, refer to the Data Communication Edition.
Do not drive two or more RS (FNC 80) and/or RS2 (FNC 87) instructions for the same port at the same time.
It is not permitted to use an "RS (FNC 80)/RS2 (FNC 87)" instruction and an "IVCK (FNC270) to IVMC (FNC275)",
"FLCRT (FNC300) to FLSTRD (FNC305)" instruction for the same port.
When using a header and terminator, set the data in the header and terminator to corresponding devices (D) before
executing the RS2 instruction. Do not change the values of the header and terminator while the RS2 instruction is
being executed.
Function Changes According to Versions
Compatible Versions
Item Function Summary
FX3G FX3U FX3GC FX3UC
Ver. 1.00
or later
Ver. 2.30
or later
Ver. 1.40
or later
Ver. 2.30
or later
ch1
Data Set Ready (DSR) Flag
Turns M8405 ON when the DR (DSR)
signal of ch1 is ON.
ch2
Data Set Ready (DSR) Flag
Turns M8425 ON when the DR (DSR)
signal of ch2 is ON.

Table of Contents

Other manuals for Mitsubishi FX3U Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi FX3U Series and is the answer not in the manual?

Mitsubishi FX3U Series Specifications

General IconGeneral
ModelFX3U Series
Program Memory64k steps
Execution Speed0.065 μs/basic instruction
TypePLC (Programmable Logic Controller)
Power Supply100-240V AC
I/O PointsUp to 384
CommunicationUSB
ExpansionSupported via expansion modules
High-Speed CountersUp to 6 channels
Analog Input/OutputAvailable via expansion modules
Temperature Range0 to 55°C
Programming LanguageLadder Logic, Structured Text
Built-in FunctionsPID control
Humidity5 to 95% (non-condensing)

Related product manuals