724
FX3G/FX3U/FX3GC/FX3UC Series
Programming Manual - Basic & Applied Instruction Edition
33 Extension File Register Control – FNC290 to FNC299
33.5 FNC294 – RWER / Rewrite to ER
2) In FX3G/FX3GC PLCs
a) When a memory cassette is connected (A memory cassette can be connected only to FX3G PLC.)
The contents (current values) of “n” extension registers (R) starting from are written (transferred) to extension
file registers having with same device numbers in a memory cassette (flash memory).
b) When a memory cassette is not connected
The contents (current values) of "n" extension registers (R) starting from are written (transferred) to
extension file registers which are stored in the EEPROM built into the PLC and have the same device
numbers.
FNC290
RWERP
S n
Command
input
E
E +1
E +2
E +n-1
+1
+2
+n-1
*1
*1 All points specified by the instruction are written (transferred).
Write
(transfer)
Extension file registers (ER)
inside memory cassette
Extension registers (R) inside
built-in RAM
S
S
S
S
S
S
S
S
S
FNC290
RWERP
S n
Command
input
E
E +1
E +2
E +n-1
+1
+2
+n-1
*1
*1 All points specified by the instruction are written (transferred).
Write
(transfer)
Extension registers (R) inside
built-in RAM
S
S
S
S
S
S
S
S
Extension file registers (ER)
inside built-in EEPROM

Table of Contents

Other manuals for Mitsubishi FX3U Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi FX3U Series and is the answer not in the manual?

Mitsubishi FX3U Series Specifications

General IconGeneral
ModelFX3U Series
Program Memory64k steps
Execution Speed0.065 μs/basic instruction
TypePLC (Programmable Logic Controller)
Power Supply100-240V AC
I/O PointsUp to 384
CommunicationUSB
ExpansionSupported via expansion modules
High-Speed CountersUp to 6 channels
Analog Input/OutputAvailable via expansion modules
Temperature Range0 to 55°C
Programming LanguageLadder Logic, Structured Text
Built-in FunctionsPID control
Humidity5 to 95% (non-condensing)

Related product manuals