MSD Servo Drive DC-AC Operation Manual
[]
Appendix
Project planning
65
Id.-No.: CA97554-001 Date: 06/2012
to glossaryto table of contents
The precharge circuit and DC link of the power supply unit must not be overloaded.
Consequently, the total power tap and total DC link capacitance of all DC-AC servo
drives must not exceed the limit values of the power supply unit. In this regard refer to
tables A.4 and A.5:
Power supply unit
Power output [kW]
DC link
capacitance
[µF]
max. DC link
capacitance [µF]
Continu-
ous
Peak
1)
G396-026 26 52
900 10000
G396-050 50 94
G396-075 75 127
4240 20000
G396 -110 110 160
1) for 10s
Table A.4 Power output and capacitances of the power supply units
DC-AC servo drive
DC link capacitance [µF]
Air cooling Liquid cooling
G393-004 60 -
G393-006 60 -
G393-008 105 -
G393-012 105 -
G393-016 / G397-020 288 288
G393-020 / G397-025 288 288
G393-024 / G397-026 504 504
G393-032 / G397-035 504 504
G393-045 / G397-053 430 900
G393-060 / G397-070 900 900
G393-072 / G397-084 900 900
G393-090 / G397-110 1060 2120
G393-110 / G397-143 2120 2120
G393-143 / G397-170 3180 4240
G393-170 / G397-210 4240 4240
Table A.5 DC link capacitances of the DC-AC servo drives
Calculation example: Feed with power supply unit
Two DC-AC servo drives G393-024, two DC-AC servo drives G393-060 and one
DC-AC servo drive G393-090 (air-cooled) are to be connected to a power supply unit
G396-075.
Calculation: 1 x 4240µF + 2 x 504µF + 2 x 900µF + 1 x 1060µF = 8108µF
Result: The power supply unit is adequately dimensioned with a maximum
precharge capacitance of 9200 µF.
NOTE: Note that not only the DC link capacitances of the DC-AC servo drives,
but also of the power supply unit, need to be considered.
A .7.5 External components
When using a power supply unit you will need additional components:
• Mains connection set (comprising mains filter, input reactor including capacitor,
step-up reactor, EMC fixings)
See MSD Servo Drive Ordering Catalog (Id. No.: CDL 29950-en).