MSD Single-Axis System Operation Manual AC-AC Servo Drive
ID no.: CA65642-001 06/2018
moog
35
Electrical installation
4.8.4 AC mains supply, Size 5 to Size 6A
Servo drive
Device connected load
1)
[kVA]
Specied mains fuse,
utilisation class gG [A]
With mains choke
(2%u
K
)
Without mains choke
G392-045
G395-053
31.2/36.7
2)
For devices of sizes
Size 5 to Size 7 a mains
choke is imperative.
3xmaximum 63
G392-060
G395-070
41.6/48.5
2)
3xmaximum 80
G392-072
G395-084
50.0/52.6
2)
3xmaximum 100
G392-090
G395-110
62/76
2)
3xmaximum 125
G392-110
G395-143
76/99
2)
3xmaximum 160
G392-143
G395-170
99/118
2)
3xmaximum 200
G392-170
G395-210
118/128
2)
3xmaximum 224
G395-250 173 3xmaximum 300
G395-325 225 3xmaximum 400
G395-450 310 3xmaximum 500
1) At 3x400V mains voltage
2) Second value applies for devices with water cooling
Table 4.7 Connected load and mains fuse (Size 5 to Size 6A)
CAUTION! Damage to the device due to incorrect operation!
• Carelessness can cause damage to the device.
For devices of sizes Size 5 to Size 7 a mains choke is imperative. Due to a different precharging
technology in these devices, it is also to be ensured that the mains choke is installed between
the servo drive and mains lter (see Figure 4.16).
K1
FN
USB 1.1
ISA00+
ISA00-
3
4
Triggering of
motor brake
GND
OSD03
2
+24 V
1
3
D1, D2
T1, T2
Ethernet
L1
PE
L2
L3
L1
L2
L3
Mains three-phase
24 V DC Power supply for
control electronic (U
V
)
24 V DC Power supply
for brake (I
IN
= 2,0 A)
-
+
-
+
1
2
1
2
Top side
X11
X10
X9
X2
X3
X4
X20
Figure 4.16 Connection example, control/mains supply for Size 5 to Size 6A
4.8.5 AC mains supply, Size 7
Servo drive
Device connected load
1)
[kVA]
Specied mains fuse, utilisation
class gG [A]
With mains choke (2%u
K
)
Without mains choke
G395-250
173
For devices of Size 7
mains choke
is imperative.
3xmaximum 300
G395-325
225 3xmaximum 400
G395-450
310 3xmaximum 500
1) At 3x400V mains voltage
2) Second value applies for devices with water cooling
Table 4.8 Connected load and mains fuse (Size 7)
CAUTION! Damage to the device due to incorrect operation!
• Carelessness can cause damage to the device.
For devices of sizes Size 5 to Size 7 a mains choke is imperative. Due to a different precharging
technology in these devices, it is also to be ensured that the mains choke is installed between
the servo drive and mains lter (see Figure 4.17).