Analog Input Module
12-6
In 0 - 5 V
current inputs
Decimal Value Input Voltage Indication
< -256 < -0.04 V Underflow LED ON
0 0 V Rated range (no LED
active)
32000 +5 V
> 32256 > +5.04 V Overflow LED ON
In 1 - 5 V
current inputs
Decimal Value Input Voltage Indication
< 6144 < 0.96 V Underflow LED ON
6400 1 V Rated range (no LED
active)
32000 +5 V
> 32256 > 5.04 V Overflow LED ON