POWER SUPPLY MODULE AND BACKUP BATTERY
General Description/Module Overview
The ACE3600 power supply module provides the other modules in the RTU with their
operating voltages via the motherboard bus.
The following power supply options are available:
DC power supply low-tier (10.8-16V)
DC power supply (10.8-16V) - provided by default with the ACE3600 RTU
DC power supply (18-72V)
DC power supply (18-72V) with battery charger
AC power supply- 100-240V
AC power supply- 100-240V with battery charger
Common characteristics of all power supply modules (not including the DC power supply low-
tier):
On/Off button on the front panel
Controlled auxiliary voltage outputs
Heat convection cooling (no need for fans)
Short protection outputs
Over heating protection
Status LEDs in the front panel
Power supply located on the leftmost slot of the frame, to the left of the CPU.
In a frame with both redundant CPUs and redundant power supplies, the third slot from the
left (between the primary CPU and the secondary CPU) is used by the redundant power
supply.
Input current protection fuse
Controlled power line enables centralized disabling of Electrically Energized relay outputs
in selectable DO modules.
Note: The DC power supply low-tier does not support radios that require input power other
than 10.8-16V. Do not use portable radios which require 7.5V input with this option.