Analog Output Module
13-5
AO Module Configuration Options
The AO module features which can be configured are listed in the table below. Some
parameters are per module and some are per output.
Table 13-1 ACE3600 AO Module Configurable Parameters
Parameter Selection Default setup Per
Module /
Output
Parameter
Setup location
AO Type Voltage/Current User Defined Output STS HW
Test/User
application
program
AO Value Voltage - 0 to 10 V
Current - 0 to 20 mA
User Defined Output STS HW
Test/User
application
program
AO
Calibration
Voltage - 2 to 10 V
Current - 4 to 20 mA
Voltage - 2 to 10 V
Current - 4 to 20 mA
Output STS HW Test
KLV &
PDV
KLV/PDV
PDV=value
KLV Output Application
Programmer I/O
link table
Mask No /Yes No Output Application
Programmer I/O
link table
Sleep Mode
Each AO module can be switched by the user application program to Sleep Mode. In Sleep
Mode, the module does not function and the power consumption is minimized. During Sleep
mode the user application program will get the predefined values for each output.