Mixed I/O Module
14-8
AI Crosstalk Rejection Better than 80 dB between any pair of inputs
AI Temperature Stability 25 PPM/ºC
AI Interference Suppression Selectable 50 or 60 Hz filtering, common mode rejection > 100 dB,
differential mode rejection > 50 dB
Diagnostic LEDs Module error LED, Status LED per each DO and DI.
Overflow and Underflow LED per each AI,
24V Plug-in status LED (AI)
AI Overflow and Underflow levels can be configured to:
Current inputs: ±20mA / 4-20 mA
Voltage inputs: ±5 V / 0-5 V /1-5 V
24 V DC Output Supports one isolated 24V A plug-in “wetting” power supply
User Connection 4 Terminal Blocks (3.5mm pitch), Maximum 18 AWG
Cable and TB Holder 40-wire cable braid with Terminal Block holder connector, 26 AWG
Module Replacement Hot swap replacement– module extraction/insertion under voltage
Input / Output Isolation DI: 2.5 kV RMS between input and module logic per IEC60255-5
DO: Between open contacts: 1kV,
between output and module logic: 1.5 kV per IEC60255-5
AI: 1.5 kV between input and module logic per IEC60255-5
Input Insulation Insulation resistance 100 MΩ @ 500 V DC per IEC60255-5
Operating Voltage 10.8-16 V DC and 3.3 V DC (from the motherboard connector)
Power Consumption Refer to Appendix D: ACE3600 Maximum Power Ratings.
Dimensions 37 mm W x 225 mm H x 180 mm D
(1.5" W x 8.7" H x 7.1" D)
Weight Approx. 0.31 Kg (0.68 Lb)