Appendix
The data in this manual are not binding and may be changed by the manufacturer without notice. Reproduction of this manual, even partial, is strictly prohibited.
035
OR02 Weekly band Enable User no no/yes
036
Band start day User Mon
Sun/Mon/Tue/Wed/Thu/Fri/
Sat
037
Band end day User Fri
Sun/Mon/Tue/Wed/Thu/Fri/
Sat
038
OR03 Hourly band Enable User no no/yes
039
Band start time User 8 0÷23/0÷59
040
Band end time User 18 0÷23/0÷59
041
Type User day by day day by day/from day to day
042
OR04 Start-up outside
band
Enable holding setpoint User no no/yes
043
Chiller setpoint User 0 °C 4÷10
044
Chiller differential User 0 °C 0÷10
045
OR05 Deactivation band 1 Enable User no no/yes
046
Band start day User 0 01 Jan./31 Dec.
047
Band end day User 0 01 Jan./31 Dec.
048
OR06 Deactivation band 2 Enable User no no/yes
049
Band start day User 9,5 01 Jan./31 Dec.
050
Band end day User 2 01 Jan./31 Dec.
051
OR07 Start-up outside
band
Heat pump setpoint User - °C 25÷55
052
Heat pump differential User 2 °C 0÷10
053
OR08 Low-noise Enable User no no/yes
054
Band start time User 23 0÷23/0÷59
055
Band end time User 7 0÷23/0÷59
MODULARITY
056
MD01 Modularity
configuration
Module index User 0 1÷10
057
Modules number User 0 1÷10 + 1 back-up
058
Modules rotation
interval
User 0 h 0÷999
059
MD02 Regulation Type User Neutral zone Neutral zone/PID
060
Probe User Bewit Bewit/Bewot/Btwot
061
Rotation type User fixed fixed/FIFO/balancing
062
MD03 Regulation Minimum OFF time User 0 s 0÷999
063
Minimum ON time User 0 s 0÷999
064
Chiller regulation band User 0 °C 0÷50
065
Heat pump regulation
band
User 0 °C 0÷50
Ref. Code Mask Field Level Value UDM Range