9.4 Draining the process water circuit
This operation is essential when, with the unit stopped and without the anti-freeze heater, the temperature in the place of
installation may fall to the point at which the water in the unit could freeze.
To drain the exchangers proceed as follows:
For units with tank and finned core exchanger:
When a pump is installed use special caution to ensure it is emptied, draining off any water that has collected in the impeller.
TAEevo Tech 402÷602 TAEevo Tech 702÷802
After having emptied the hydraulic system open
the bleed and drain cocks and wait until all the
water in the storage tank is drained off.
After having emptied the hydraulic system open the drain cocks and the bleed cock and wait until all the water in the
storage tank is drained off.
D
B
C
F
A
B
D
B
C
F
A
B
Drain cock
Bleed cock