OPERATING AND MAINTENANCE MANUAL
Chapter 7 - Electronic controller
TAEevo Tech 015÷802 60 Hz UL
49
The data in this manual are not binding and they can be modified by the manufacturer without notice. Reproduction of this manual is strictly prohibited
EN
ENGLISH
7.11.20 Phase monitor alarm
7.11.21 Compressors maintenance alarm
7.11.22 Pumps maintenance alarm
7.11.23 EEprom alarm
For unit configuration alarms “ACF1÷ACF9” and “AC10÷AC14”, contact technical assistance.
Display labels meaning ALc1
Cause of trip Phase monitor alarm
Reset Phase monitor not active alarm
Reset automatic - becomes manual after AL42 trips / hour (reset procedure in
functions menu). Recorded in alarms log exclusively with manual reset.
Icon Flashing
Action Alarm relay + buzzer activated
Regulators
Alarm Relay + buzzer activated
Other loads Off
Display labels meaning C1Mn (compressor 1 maintenance request)
C2Mn (compressor 2 maintenance request)
C3Mn (compressor 3 maintenance request)
C4Mn (compressor 4 maintenance request)
Cause of trip Compressor running hours > programmed hour meter setting
Reset Running hours reset (in functions menu, “Hour” function, hold down “set”
button for several seconds)
Reset Manual
Icon Flashing
Action Alarm relay + buzzer activated
Regulators
Alarm Relay + buzzer activated
Other loads Follow their control
Display labels meaning AEP1 (evaporator water pump maintenance request)
AEP2 (evaporator second pump maintenance request)
Cause of trip Pump running hours > programmed hour meter setting
Reset Running hours reset (in functions menu, “Hour” function, hold down “set”
button for several seconds)
Reset Manual
Icon Flashing
Action Alarm relay + buzzer activated
Regulators
Alarm Relay + buzzer activated
Other loads Follow their control
Display labels meaning AEE
Cause of trip Failed write to Eeprom
Reset ------
Reset Manual
Icon Flashing
Action Alarm relay + buzzer activated
Regulators
Other loads Off