OPERATING AND MAINTENANCE MANUAL
Chapter 6 - Starting
TAEevo Tech 015÷802 60 Hz UL
31
The data in this manual are not binding and they can be modified by the manufacturer without notice. Reproduction of this manual is strictly prohibited
EN
ENGLISH
13. If at the time of first startup the ambient temperature is high and the water temperature in the hydraulic circuit is
significantly higher than the operating value (e.g. 25-30°C / 77-86°F) this means that the chiller is starting in
overloaded conditions resulting in possible tripping of the protections. To reduce the overload you can
progressively close (without closing it completely!) a valve at the chiller outlet to reduce the flow rate of water
passing through it. As the water temperature in the hydraulic circuit approaches the working value, the valve can
be re-opened.
14. The unit is now ready to start operating.
If the thermal load is lower than that produced by the unit, the water temperature decreases until it reaches the
setpoint value set following the instructions. Chapter 7 Electronic controller
Once the SETPOINT value has been reached the controller monitoring the water inlet temperature will stop the
compressor. In these conditions the water pump runs constantly.