73
The data in this manual are not binding and they can be modified by the manufacturer without notice. Reproduction of this manual is strictly prohibited
EN
ENGLISH
7.41 Parameters description-settings
The following is a list of all the programmable parameters complete with their associated access levels.
U= User level
S= Service level
C= Manufacturer level
ATTENTION
Ensure these instructions are observed in full to avoid incorrect operation of the unit.
7.41.1 Description of parameters
Parameter Level Description Min. Max. UM Resolution
Thermoregulator
ST01 U Chiller setpoint.
Enables setting of the working setpoint in chiller mode.
ST02 ST03 °C
°F
Dec
Int
ST02 U Chiller minimum set.
Establishes the minimum limit that can be utilised to set the
chiller working setpoint.
-50.0
-58
ST01 °C
°F
Dec
Int
ST03 C Chiller maximum set.
Establishes the maximum limit that can be utilised to set the
chiller working setpoint.
ST01 110.0
230
°C
°F
Dec
Int
ST04 C Heat pump setpoint.
Enables setting of the working setpoint in heat pump mode.
ST05 ST06 °C
°F
Dec
Int
ST05 C Heat pump minimum set.
Establishes the minimum limit that can be utilised to set the heat
pump working setpoint.
-50.0
-58
ST04 °C
°F
Dec
Int
ST06 C Heat pump maximum set.
Establishes the maximum limit that can be utilised to set the heat
pump working setpoint.
ST04 110.0
230
°C
°F
Dec
Int
ST07 U Control steps activation band in chiller mode. 0.1
0
25.0
45
°C
°F
Dec
Int
ST08 C Control steps activation band in heat pump mode. 0.1
0
25.0
45
°C
°F
Dec
Int
ST09 C Defines the probe for temperature control of the unit in chiller
mode:
0= Evaporator inlet NTC temperature probe
1= Evaporator outlet NTC temperature probe no. 1
2= Evaporator outlet NTC temperature probe no. 2
3= Common evaporator outlet NTC temperature probe
4= Remote terminal temperature probe no. 1
5= Remote terminal temperature probe no. 2
05