OPERATING AND MAINTENANCE MANUAL
Chapter 3 - Technical data
TAEevo Tech 015÷802 60 Hz UL
19
The data in this manual are not binding and they can be modified by the manufacturer without notice. Reproduction of this manual is strictly prohibited
EN
ENGLISH
* at distance of 1 m (3.2 FT)
** global
Test conditions
Noise levels refer to operation of the unit at full load in nominal conditions.
Sound pressure level in hemispherical irradiation conditions at a distance of 1 m (3.2 FT) from the condensers side of the unit
and height of 1.6 m (5.2 FT) from the ground. Values with tolerance of ± 2 dB.
Sound pressure level: according to ISO 3744.
Fan Lp dB(A) * Lw dB(A) **
TAEevo Tech 015 axial 69,5 82,5
TAEevo Tech 020 axial 68,9 81,9
TAEevo Tech 031 axial 69,6 82,6
TAEevo Tech 051 axial 70,7 83,7
TAEevo Tech 081 axial 70,9 83,9
TAEevo Tech 101 axial 72,0 85,0
TAEevo Tech 121 axial 71,2 84,2
TAEevo Tech 161 axial 72,1 85,1
TAEevo Tech 201 axial 74,2 87,2
TAEevo Tech 251 axial 74,1 87,1
TAEevo Tech 301 axial 75,6 88,6
TAEevo Tech 351 axial 75,3 88,3
TAEevo Tech 381 axial 78.0 91,0
TAEevo Tech 401 axial 80.2 93,2
TAEevo Tech 402 axial 79,5 92,5
TAEevo Tech 502 axial 79,6 92,6
TAEevo Tech 602 axial 79,3 92,3
TAEevo Tech 702 axial 79.4 92,4
TAEevo Tech 802 axial 80.6 93,6