Technical Data
User manual 9000-41011-0200000_hdb_en_20 26 / 92
4.1.2.3 Electrical safety
4.1.2.4 EMC-interference
4.1.2.5 EMC-emissions
4.1.2.6 EMC-immunity
9000-41190-0000110 Vibration test 3 axis, 60 minutes 2-17.8Hz:
±1.6 mm
17.8-500 Hz:
2,0g
Shock test 1 shock/s, 3 axis,
3 pos. & 3 neg. per
axis
15 g / 11ms
sinusoidal
with single
channel out-
put;
20 g / 11ms
sinusoidal
with multi
channel out-
put
Art.-No. Parameter Conditions Value
Parameter Conditions Value
Degree of protection EN 60529 IP20
Pollution degree 2
Overvoltage category EN 60950-1 II
Overvoltage category EN 50178 III
Parameter Conditions Value
Low-voltage power supplies, d.c.
output - Electromagnetic
compatibility (EMC)
EN 61204-3 Emission class: B
(residential,commercial and
light industry)
Immunity: High severity
level (Industrial)
Parameter Conditions Value
Radiated emissions EN 55022
CISPR 22
30 ... 1000 MHz
Class B
Conducted emissions EN 55011
CISPR 11:2009
0.15 ... 30 MHz
0.01 ... 30 MHz
Class B
Harmonic currents Class A
Voltage fluctiation, flicker passed
Parameter Conditions Value
Electrostatic discharge EN 61000-4-2 Contact: ±6 kV Criterion A
Air: ±8 kV Criterion A
Electromagnetic RF Field EN 61000-4-3 80 MHz ... 2 GHz, 10 V/m,
Criterion A
Fast transient (Burst) EN 61000-4-4 Input: ±2 kV Criterion A
Output: ± 2kV Criterion A
Surge voltage EN 61000-4-5 Line to Line (DM)
±0.5 kV / ±1 kV Criterion A
Conducted disturbances EN 61000-4-6 0.15 ... 80 MHz, 10 Vemf
Criterion A