Technical Data
User manual 9000-41011-0200000_hdb_en_20 45 / 92
4.5.1.3 Performance record
All efficiencies and voltage drops at 50% load.
4.5.2 Environmental characteristics
4.5.2.1 Climatic
Article Art.-No. Efficiency Voltage drop per
channel
Mico Pro fix 1.2 9000-41011-0200000 99,0 % 0,23 V
Mico Pro fix 1.4 9000-41011-0400000 99,4 % 0,16 V
Mico Pro fix 1.6 9000-41011-0600000 99,5 % 0,13 V
Mico Pro fix 1.8 9000-41011-0800000 99,5 % 0,11 V
Mico Pro fix 1.10 9000-41011-1000000 99,6 % 0,10 V
Mico Pro fix 1.16 9000-41011-1600000 99,6 % 0,09 V
Mico Pro fix 2.2 9000-41012-0200000 99,3 % 0,18 V
Mico Pro fix 2.4 9000-41012-0400000 99,3 % 0,17 V
Mico Pro fix 2.6 9000-41012-0600000 99,4 % 0,15 V
Mico Pro fix 4.2 9000-41014-0200000 99,1 % 0,21 V
Mico Pro fix 4.4 9000-41014-0400000 99,4 % 0,16 V
Mico Pro fix 4.6 9000-41014-0600000 99,4 % 0,15 V
Parameter Conditions Value
Relative humidity 5 ... 85 %
Storage temperature -40 ... +80 °C
Climate class IEC/EN 60721-3-3 3K3
Surrounding air temperature
range (T
a
)
-25 ... +55 °C
Variants installation height
Art.-No. Conditions Value
9000-41011-0200000 Above sea level,
without any restrictions
-500 m ... 6000 m
9000-41011-0400000
9000-41011-0600000
9000-41012-0200000
9000-41012-0400000
9000-41012-0600000
9000-41014-0200000
9000-41014-0400000
9000-41014-0600000
9000-41011-0800000 Above sea level,
without any restrictions
-500 m ... 4000 m
Above sea level,
max. 6 A trigger current full load per
channel
4000 m ... 6000 m