Technical Data
User manual 9000-41011-0200000_hdb_en_20 43 / 92
NOTE
A high-energy impulse (surge) applied to the output of the Mico Pro modules
can cause short-term voltage interruption (max. 3 ms). This protects the con-
nected loads. Mico Pro detects within this time, whether a faulty short circuit
or a high-energy impulse occurred. If there is no short circuit, Mico Pro will be
switched on again.
9000-41012-0400000 Tripping current (I
N
) Full load per channel 4 A (+20%)
Output current (I
) Full load all channels 8 A
Power-up delay Per channel to avoid
inrush current peaks
75 ms
9000-41012-0600000 Tripping current (I
N
) Full load per channel 6 A (+20%)
Output current (I
) Full load all channels 12 A
Power-up delay Per channel to avoid
inrush current peaks
75 ms
9000-41014-0200000 Tripping current (I
N
) Full load per channel 2 A (+20%)
Output current (I
) Full load all channels 8 A
Power-up delay Per channel to avoid
inrush current peaks
75 ms
9000-41014-0400000 Tripping current (I
N
) Full load per channel 4 A (+20%)
Output current (I
) Full load all channels 16 A
Power-up delay Per channel to avoid
inrush current peaks
75 ms
9000-41014-0600000 Tripping current (I
N
) Full load per channel 6 A (+20%)
Output current (I
) Full load all channels 24 A
Power-up delay Per channel to avoid
inrush current peaks
75 ms
Variants Output: Number of channels, Tripping current (I
N
), Output current (I
),
Power-up delay
Art.-No. Parameter Conditions Value
Characteristics: Disconnecting characteristics | Tripping current (I
N
)
For Mico Pro fix Tripping current (I
N
) 2 A to 10 A
Disconnection time at short circuit: approx. 5 ms
Fig. 4-11: Disconnecting characteristics | Tripping current

Table of Contents