EasyManua.ls Logo

Murr Elektronik Mico Pro Series - Page 58

Murr Elektronik Mico Pro Series
92 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical Data
User manual 9000-41011-0200000_hdb_en_20 58 / 92
NOTE
A high-energy impulse (surge) applied to the output of the Mico Pro modules
can cause short-term voltage interruption (max. 3 ms). This protects the con-
nected loads. Mico Pro detects within this time, whether a faulty short circuit
or a high-energy impulse occurred. If there is no short circuit, Mico Pro will be
switched on again.
Output variants: Number of channels, Tripping current (I
N
), Output current (I
),
Tripping current setting range, Power-up delay
Art.-No. Parameter Conditions Value
9000-41091-0101000 Number of channels 1
Tripping current (I
N
) Full load 10 A (+20%)
Tripping current set-
ting range
Selectable for
each channel
1 A, 2 A, 3 A, 4 A, 5 A,
6 A, 7 A, 8 A, 9 A, 10 A
9000-41091-1102000 Number of channels 1
Tripping current (I
N
) Full load 20 A (-5% ... +15%)
Tripping current set-
ting range
Selectable for
each channel
11 A, 12 A, 13 A,
14 A, 15 A, 16 A,
17 A, 18 A, 19 A, 20 A
9000-41092-0101000 Number of channels 2
Tripping current (I
N
) Full load per
channel
10 A (+20%)
Output current (I
) Full load all
channels
20 A
Tripping current set-
ting range
Selectable for
each channel
1 A, 2 A, 3 A, 4 A, 5 A,
6 A, 7 A, 8 A, 9 A, 10 A
Power-up delay Per channel to
avoid inrush
current peaks
75 ms
9000-41094-0101000 Number of channels 4
Tripping current (I
N
) Full load per
channel
10 A (+20%)
Output current (I
) Full load all
channels
40 A
Tripping current set-
ting range
Selectable for
each channel
1 A, 2 A, 3 A, 4 A, 5 A,
6 A, 7 A, 8 A, 9 A, 10 A
Power-up delay Per channel to
avoid inrush
current peaks
75 ms

Table of Contents