Description of functions - Start up 19
FIGHTER 1330
Inspection
11. Set the heat pump's operating type to External
control in menu 0.2.1.
12. Remove the strap for compressor A (KPRAA).
13. Compressor A starts. Note there may be a slight
delay of a few minutes before starting. See menu
0.1.1 to see the time to start.
14. Check the temperature difference on the heat
medium in menu 5.2.1. Nominal difference is 5 to
10 °C.
15. Check the temperature difference on the brine
medium in menu 5.2.2. Nominal difference is 2 to
5 °C.
16. Reset the strap for compressor A (KPRAA).
17. Remove the strap for compressor B (KPRAB).
18. Compressor B starts. Note there may be a slight
delay of a few minutes before starting. See menu
0.1.2 to see the time to start.
19. Check the temperature difference on the heat
medium in menu 5.3.1. Nominal difference is 5 to
10 °C.
20. Check the temperature difference on the brine
medium in menu 5.3.2. Nominal difference is 2 to
5 °C.
21. Reset the strap for compressor B (KPRAB).
22. Reset all settings by selecting Extended in menu
5.4.10. Note that the setting returns to Off as soon
as the heat pump has made the factory setting.
23. Set the power switch (8) in position ”0”.
24. Remove both straps (KPRAA and KPRAB).
When all heat pumps have undergone this inspection,
continue with “Description of functions” - “Start up” >
“Start up with a FIGHTER 1330” or if several FIGHERS
1330 are connected “Description of functions” - “Start
up” > “Start up with several FIGHTER 1330s in a sys-
tem”
See “Dealing with malfunctions” at the end of the
booklet in the event of any problems at start-up.