Description of functions - Start up
FIGHTER 1330
20
1. FIGHTER 1330 is delivered as the Master. Other
units in the system must be selected as unique sla-
ves. This is done according to the instructions in
Description of Functions - Start up > Master/Slave.
It is extremely important that this is done for all
units when the following settings are made.
2. Start all the heat pumps by turning the power switch
(8) to the 1 position. The slaves will now flash Con-
necting, while the Master is in screen saver mode.
3. Deactivate the screen saver on the Master by hol-
ding down the button in the far left corner and the
enter button for approximately 8 seconds. (See the
section the Description of Functions - Start up >
Screensaver.)
4. Set the Master in the Service position from menu
8.1.1. (See the example in Control > Changing para-
meters.)
5. Set each connected unit's operating type, i.e. which
pumps should produce hot water and/or hea-
ting. This is done in menu 0.2.1. (See the section
Description of Functions - Start up > ”Operating
type selection”.) As long as Off is selected as the
operating type, no communication with the Slave
will occur, however, as soon as the operating type
is changed to something other than Off, the Slave's
display will stop flashing Connecting and will enter
Screen saver mode.
6. Check that all connected heat pumps display the
correct Slave number on the display. If this is not the
case, check that all communication cables are cor-
rectly connected and shutoff all heat pumps. Now
restart the Slaves and then the Master. Should the
wrong Slave number be displayed or a display conti-
nues to flash Connecting - start again with the Mas-
ter/Slave settings in point 1.
7. Continue with the start up settings with the help of
Description of Functions - Basic Functions. Connect
and configure the pertinent functions for the instal-
lation.
Start up with several FIGHTER
1330s in a system
1. Start the heat pump by turning the power switch
(8) to the 1 position. The unit will now enter screen
saver mode and the text Master will be shown on
the bottom row of the display.
When only Connecting flashes the heat pump this
may be because the heat pump is set as a Slave.
If so, set the unit as the Master according to the
instructions in Description of Functions - Start up >
Master/Slave.
2. Deactivate the screen saver by holding down the
button in the far left corner and the enter button
for approximately 8 seconds. (See the section the
Description of Functions - Start up > Screensaver.)
3. Set in the Service position from menu 8.1.1. (See
the example in Control > Changing parameters.)
4. Set the heat pump's operating type, i.e. whether
the heat pump should produce hot water and/or
heating. This is done in menu 0.2.1. (See the sec-
tion Description of Functions - Start up > Operating
type selection.)
5. Continue the start up settings with the help of
Description of Functions - Basic Functions. Con-
nect and configure the pertinent functions for the
installation.
Start up with a FIGHTER 1330