Description of functions - Basic functions
25
FIGHTER 1330
Heating
Operating mode
The menu is accessible via the operat-
ing mode button. Whether heat produc-
tion is permitted is selected here and if
so whether the electrical additional heater
may be used.
Menu 2.1 Curve slope
The selected curve slope for the heating curve
is shown here. The value is adjustable between
curve 1 and 15, or in Own curve. The values for
own curve are set in menu 2.6.0. The factory set-
ting is 9.
Menu 2.2 Offset heating curve
The chosen offset for the heating curve is shown
here. The value is adjustable between -10 and
+10. NOTE! The value cannot be changed using
the plus and minus buttons, only by using the Off-
set heating curve knob on the Master unit.
Menu 2.3 Min. flow temp.
The set minimum level for the flow temperature to
the heating system is shown here. The calculated
supply temperature never drops below this level
irrespective of the outdoor temperature, curve
slope or offset heating curve. The value is adjust-
able between 2 and 65 °C. The factory setting is
15 °C.
Menu 2.4 Max. flow temp.
The set maximum level for the supply tempera-
ture to the heating system is shown here. The
calculated supply temperature never exceeds
this level irrespective of the outdoor temperature,
curve slope or offset heating curve. The value is
adjustable between 10 and 80 °C. The factory
setting is 55 °C.
Quick guide - menu settings heat production
The outline diagram with docking instruc-
tions is available at www.nibe.com