Oil boiler
Description of functions - Basic functions
31
FIGHTER 1330
Menu 9.1.8 Additive
Whether additional heat is to be engaged is set
here. The options are: Off, Electricity, Oil or Elec-
tri/Oil. The factory setting is Off.
In order for the oil boiler to be active the option
Oil or Electri/Oil must be selected in this menu.
When Electri/Oil is selected, oil is used for addi-
tional output when the input Tariff A (TA) is bro-
ken, otherwise electricity is used.
Menu 8.2.5 Additive start value
Here you select at which degree-minute setting
the first additional heater step shall start for heat-
ing. The value is adjustable between -3000 and 0.
The factory setting is -500.
Menu 6.3.1 Oil Boiler time
Number of hours the oil boiler shall be active. The
value can be set between 1 and 24 hours. The
factory setting is 12 hours.
Menu 6.3.2 Start temp. shunt
Here you select the temperature on the boiler
sensor (PG) at which the boiler shunt (SV-P)
shall start to regulate. Adjustable between 10 and
90 °C. The factory setting is 55 °C.
Quick guide - menu settings oil boiler
The outline diagram with docking instruc-
tions is available at www.nibe.com