5.0 Heat pump
U
U
U
U
Menu 5.3.0 Compressor module B
The current mode of compressor module B is
shown here:
”Heat / Hot water / Ext. control / Waiting / Alarm
/ Off”. Pressing the enter button takes you to the
sub-menus that show the temperatures and statis-
tics for compressor module B.
Menu 5.3.1 Heating flow/return
The internal flow (VBFB) and return temperatures
(VBRB) are shown here for the heat medium to the
compressor module B.
Menu 5.3.2 Brine in/out
The current incoming (KBinB) and outgoing tem-
perature (KButB) are shown here for brine to the
compressor module B.
Menu 5.3.3 Hot gas temperature
The current hot gas temperature for compressor
module B at the sensor (HGB) is shown here.
Menu 5.3.4 Overheating temp.
The current bulb temperature for compressor mod-
ule B at the sensor (BB) is shown here.
Menu 5.3.5 Liquide line temp.
The current fluid line temperature for compressor
module B at the sensor (VLB) is shown here.
Menu 5.3.6 Tot. starts compr. B
The number of times that compressor B has been
started since the first start up is shown here. The
value is saved in the microprocessor and thus is
not reset even when the heat pump is switched off
using the main power switch.
Menu 5.3.7 Opera.time compr. B
The number of hours that compressor B has been
in operation since the first start up is shown here.
The value is saved in the microprocessor and thus
is not reset even when the heat pump is switched
off using the main power switch.
Menu 5.3.8 Return
Pressing the enter button returns you to menu
5.3.0.
Menu 5.4.0 Settings
Pressing the enter button takes you to the settings
for the unit selected in menu 5.1.
Menu 5.4.1 Max.heat returntemp.
The maximum permitted heating medium-return
temperature for the compressor is displayed here.
Menu 5.4.2 Min. brine out
The minimum permitted brine temperature out from
the heat pump. Can be set between -10 and +15 °C
or Off. The factory setting is -8 °C.
Menu 5.4.3 Max. brine in
Maximum permitted brine temperature in to the
heat pump. Can be set between -10 and +40 °C or
Off. The factory setting is Off.
Menu 5.4.4 Level monitor
Select here if an external brine pressostat, level
sensor or flow sensor is connected to the “EBV
card”.
Can be set to On (NC), On (NO) or Off. The factory
setting is Off.
Menu 5.4.5 Start to start time
The shortest time from start to start of the same
compressor is set here. Can be set between 20
and 60 minutes. The factory setting is 20 minutes.
Menu 5.4.6 Oper. mode brinepump
The operating mode for the brine pump is set here.
Selectable options are:
Intermittent: The brine pump starts 20 seconds
before and stops 20 seconds after the compressor.
Continuous: Continuous operation.
10 days cont: Continuous operation for 10 days.
The pump then switches to intermittent operation.
The factory setting is Intermittent.