Electrical connection
15
For the Installer
FIGHTER 360P
FIGHTER 360P must be installed via an isolator
switch. Other electrical equipment, except the outdoor
sensor and the current sensors, are connected at the
factory.
Disconnect the heat pump before insulation testing
the house wiring.
FIGHTER 360P can be connected to a single phase
power suppply.
The connection is made according to the illustrations
below depending on the desired maximum output.
Max phase current, single phase
The knob (101) should always be set to position D
when using a single phase power supply.
The two immersion heaters have a total maximum out-
put of 13.5 kW. The power rating as set at the factory
is 7.5 kW, which corresponds to position C on the knob
(101) on the load monitor card (2).
Connection
Single phase connection
Output as set at the factory
NOTE!
Reset the temperature limiter,
it may have tripped during transport.
NOTE!
The switch (8) must not be moved
from 1 or “ ” until the boiler has
been filled with water. Otherwise the
temperature limiter, thermostat,
compressor and the immersion heater
can be damaged.
The automatic heating control system, circulation
pump (16) and its cabling, are internally fuse protected
with a miniature circuit breaker (7).
The supply to the heat pump is connected to termi-
nal (9) via a strain relief. Connection must not be car-
ried out without the permission of the electricity sup-
plier and under the supervision of a qualified electri-
cian. The cable entry conduit is dimensioned for cable
with a max Ø 19 mm.
The power is controlled via a contactor which is oper-
ated by a microprocessor.
The temperature limiter (6) cuts off the supply to the
immersion heater if the temperature rises to between
90 and 100 °C; it can be manually reset by pressing
the button on the temperature limiter.