5 Parameter
BU 0250 en-3021 109
Pos: 349 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P300- P399/Parameter P353 Busz ustand über PLC @ 9\mod_144836383 4229_388.docx @ 266393 @ @ 1
P353
Bus status via PLC
(Bus status via PLC)
S
0 ... 3
{ 0 }
This parameter can be used to determine how the control word (STW) for the master function and
the status word (ZSW) of the frequency inverter undergo further processing by the PLC.
0 = Off: The control word (STW) of the master function (P503≠0) and the status word (ZSW)
undergo further processing by the PLC without change.
1 = STW for broadcast: The control word (STW) for the master value function (P503≠ 0) is set
by the PLC. In order to do this, the control word must be redefined in the PLC using
process value "34_PLC_Busmaster_Control_word".
2 = ZSW for bus: The status word (ZSW) of the frequency inverter is set by the PLC. In order
to do this, the status word must be redefined in the PLC using process value
"28_PLC_status_word".
3 = STW Broadcast&ZSWBus: See setting 1 and 2
Pos: 350 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P300- P399/Parameter P355 PLC I nteger Sollwert @ 9\mod_14483 64290270_388.doc x @ 266496 @ @ 1
P355 [-01]
...
[-10]
PLC Integer Setpoint
(PLC Integer Setpoint)
S
0x0000 … 0xFFFF
all = { 0 }
Data can be exchanged with the PLC via this INT array. This data can be used by the appropriate
process variables in the PLC.
Pos: 351 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P300- P399/Parameter P356 PLC Long So llwert @ 9\mod_14483763 05117_388.doc x @ 266562 @ @ 1
P356 [-01]
...
[-05]
PLC Long Setpoint
(PLC Long Setpoint)
S
0x0000 0000 …
0xFFFF FFFF
all = { 0 }
Data can be exchanged with the PLC via this DINT array. This data can be used by the
appropriate process variables in the PLC.
Pos: 352 /Anleitungen/ Elektronik/F U und Starter/5. Parameter /Parameterauflis tung (P000 ...)/ P300-P399/Parameter P360 PLC Anzei gewert @ 9\mod_14483766 91352_388.doc x @ 266635 @ @ 1
P360 [-01]
...
[-05]
PLC display value
(PLC display value)
S
-2 000 000,000 …
2 000 000.000
all = { 0.000 }
The parameter is only used to display the PLC Date. Via the corresponding process variables,
this parameter can be written by the PLC. The values are not saved!
Pos: 353 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/ P300-P399/Parameter P370 PLC Status @ 9\mod_1448 364654868_388.doc x @ 266529 @ @ 1
P370
PLC Status
(PLC Status)
S
0 … 63
dec
ParameterBox:
0x00 … 0x3F
SimpleBox / ControlBox:
0x00 … 0x3F
all = { 0 }
Displays the actual status of the PLC.
Bit 0 = P350=1: Parameter P350 was set in the "Activate internal PLC" function
Bit 1 = PLC active: The internal PLC is active.
Bit 2 = Stop active: The PLC program is in "Stop" status.
Bit 3 = Debug active: The error checking of the PLC program runs.
Bit 4 = PLC error: The PLC has an error, but PLC user errors 23.xx are not displayed here.
Bit 5 = PLC halted: The PLC program has been halted (Single Step or Breakpoint).