NORDAC LINK (SK 250E-FDS ... SK 280E-FDS) – Users Manual for Frequency Inverters as Field Distributors
86 BU 0250 en-3021
Pos: 244 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ P1xx Basisparameter @ 0\mod_1327574618174_388. docx @ 7458 @ 3 @ 1
5.2.2 Basic parameters
Parameter
{factory setting}
Setting value / Description / Note Supervisor
Parameter
set
Pos: 245 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P100- P199/Parameter P100 – Par ametersatz @ 0\mod_13275747 57831_388.doc x @ 7481 @ @ 1
P100
Parameter set
(Parameter set)
S
0 ... 3
{ 0 }
Selection of the parameters sets to be parameterised. 4 parameter sets are available. The
parameters to which different values can also be assigned in the 4 parameter sets are known as
"parameter set-dependent" and are marked with a "P" in the header in the following descriptions.
The operating parameter set is selected using appropriately parametrised digital inputs or by
means of BUS actuation.
If enabled via the keyboard (SimpleBox, ControlBox, PotentiometerBox or ParameterBox), the
operating parameter set will match the settings in P100.
Pos: 246 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P100- P199/Parameter P101 – Par am.-Satz kopieren @ 0\mod_1327 574829893_388.doc x @ 7504 @ @ 1
P101
Copy parameter set
(Copy parameter set)
S
0 ... 4
{ 0 }
After confirmation with the OK / ENTER key, a copy of the parameter set selected in P100
>Parameter set< is written to the parameter set dependent on the value selected here
0 = Do not copy
1 = Copy actual to P1: Copies the active parameter set to parameter set 1
2 = Copy actual to P2: Copies the active parameter set to parameter set 2
3 = Copy actual to P3: Copies the active parameter set to parameter set 3
4 = Copy actual to P4: Copies the active parameter set to parameter set 4
Pos: 247 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P100- P199/Parameter P102 – Hoc hlaufzeit @ 0\mod_13275 74880847_388.doc x @ 7527 @ @ 1
P102
Acceleration time
(Acceleration time)
P
0 ... 320.00 sec
{ 2.00 }
The start-up time is the time corresponding to the linear frequency rise from 0
maximum frequency (P105). If an actual setpoint of <100 % is being used, the acceleration time is
reduced linearly according to the setpoint which is set.
The acceleration time can be extended by certain circumstances, e.g. FI overload, setpoint lag,
smoothing, or if the current limit is reached.
NOTE:
Care must
be taken that the parameter values are realistic. A setting of P102 = 0 is not
permissible for drive units!
Notes on ramp gradient:
Amongst other things, the ramp gradient is governed by the inertia of the rotor.
A ramp with a gradient which is too steep may result in the "inversion" of the motor.
In general, extremely steep ramps (e.g.: 0 - 50 Hz in < 0.1
s) should be avoided, as may cause
damage to the frequency inverter.
Pos: 248 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/ P100-P199/Parameter P103 – Br emszeit @ 0\mod_1327574939 362_388.docx @ 7550 @ @ 1
P103
Braking time
(Braking time)
P
0 ... 320.00 sec
{ 2.00 }
The braking time is the time corresponding to the linear
frequency reduction from the set
maximum frequency to 0 Hz (P105). If an actual setpoint <100
% is being used, the deceleration
time reduces accordingly.
The braking time can be extended by certain circumstances, e.g. by the selected >Switch-off
mode< (P108) or >Ramp smoothing< (P106).
NOTE:
Care must be taken that the parameter values are realistic. A setting of P103 = 0 is not
permissible for drive units!
Notes concerning ramp steepness: see parameter (P102)
Pos: 249 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P100- P199/Parameter P104 – Mini male Frequenz @ 0\mod_13275 75009471_388.doc x @ 7573 @ @ 1