NORDAC LINK (SK 250E-FDS ... SK 280E-FDS) Users Manual for Frequency Inverters as Field Distributors
110 BU 0250 en-3021
Pos: 355 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ P4xx Steuerklemmen @ 0\ mod_1327678262854_388. docx @ 9027 @ 3 @ 1
5.2.5 Control terminals
Parameter
{factory setting}
Setting value / Description / Note Supervisor
Parameter
set
Pos: 356 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P400- P499/Parameter P400 Fkt. Sollwertei ngang [SK 2xxE-FDS] @ 12\mod_14672 70460325_388.doc x @ 334560 @ @ 1
P400 [-01]
...
[-09]
Function Setpoint inputs
(Function of setpoint inputs)
P
0 ... 36
{ [-01] = 0 }
{ [-02] = 0 }
{ [-03] = 0 }
{ [-04] = 0 }
{ [-05] = 1 }
{ [-06] = 0 }
{ [-07] = 1 }
{ [-08] = 0 }
{ [-09] = 0 }
[-01]
Analog input 1, Function of analog input 1 integrated into the FI
[-02]
Analog input 2, Function of analog input 2 integrated into the FI
[-03]
External analog input 1, AIN1 of the first I/O extension (SK xU4-IOE)
[-04]
External analog input 2, AIN2 of the first I/O extension (SK xU4-IOE)
[-05]
Setpoint module
[-06]
Digital input 2, can be set to pulse signal evaluation via P420 [-02] =26 or 27. The pulses
are then evaluated in the FI as an analogue signal according to the function which is set
here.
[-07]
Digital input 3, can be set to pulse signal evaluation via P420 [-03] =26 or 27. The pulses
are then evaluated in the FI as an analogue signal according to the function which is set
here.
[-08]
External A.in. 1 2nd IOE, "External analog input 1 2nd IOE", AIN1 of the second I/O
extension (SK xU4-IOE) (= Analog input 3)
[-09]
External A.in. 2 2nd IOE, "External analog input 2 2nd IOE", AIN2 of the second I/O
extension (SK xU4-IOE) (= Analog input 4)
... Setting values below.
Pos: 357 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P400- P499/Parameter P400 Par ameterwerte [SK 1x0E, SK 2 xxE-FDS] @ 9\mod_1448282266832_3 88.docx @ 265611 @ @ 1
For standardisation of actual values: Section 8.8 "Standardisation of setpoint / target values".
0 = Off, the analogue input has no function. After the
FI has been enabled via the control
terminals, it will supply the set minimum frequency (P104).
1 =
Setpoint frequency, the given analogue range (P402/P403) varies the output frequency
between the set minimum and maximum frequencies (P104/P105).
2 =
Frequency addition **, the supplied frequency value is added to the setpoint.
3 =
Frequency subtraction **, the supplied frequency value is subtracted from the setpoint.
4 =
Minimum frequency, setting for minimum frequency of frequency inverter
Lower limit: 1 Hz
Standardisation: 0 - 100% of P104
5 =
Maximum frequency, setting for maximum frequency of frequency inverter
Lower limit: 2 Hz
Standardisation: 0 - 100% of P105
6 = Actual value process controller *, activates the process controller
, analogue input is
connected to the actual value encoder (compensator, air can, flow volume meter, etc.).
The mode is set via the DIP switches of the I/O extension or in (P401).
7 =
Setpoint process controller *, as for Function 6, however, the setpoint is specified (e.g.
by a potentiometer). The actual value must be specified using another input.
8 =
Actual PI frequency *,
is required to build up a control loop. The analogue input (actual
value) is compared with the setpoint (e.g. fixed frequency). The output frequency is
adjusted as far as possible until the actual value equals the setpoint. (see control
variables P413...P414)
9 =
Actual freq. PI limited *, "Actual frequency PI limited“, as for function 8 "Actual frequency
PI", however the output frequency cannot fall below the programmed minimum frequency
value in Parameter P104. (no change to rotation direction)
10 =
Actual freq. PID monitored *, "Actual frequency PID monitored", as for function 8 Actual
frequency PI", however the FI switches the output frequency off when the minimum
frequency P104 is reached
11 =
Torque current limit, "Torque current limited" depends on parameter (P112). This value
corresponds to 100% of the setpoint value. When the set limit value is reached, there is a
reduction of the output frequency at the torque current limit.