EasyManua.ls Logo

Nord Drivesystems NORDAC LINK SK250E-FDS - Messages

Nord Drivesystems NORDAC LINK SK250E-FDS
212 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
NORDAC LINK (SK 250E-FDS ... SK 280E-FDS) Users Manual for Frequency Inverters as Field Distributors
166 BU 0250 en-3021
Pos: 574 /Anleitungen/ Elektronik/F U und Starter/6. Meldungen zu m Betriebszustand/Me ldungen @ 3\mod_1361803071 259_388.docx @ 59851 @ 2 @ 1
6.3 Messages
Pos: 575 /Anleitungen/ Elektronik/F U und Starter/6. Meldungen zu m Betriebszustand/ Störmeldungen (Tabel lenüberschrift) @ 3\mod_1361803456862_388. docx @ 59874 @ 5 @ 1
Error messages
Display in the
SimpleBox / ControlBox
Fault
Text in the ParameterBox
Cause
Remedy
Group Details in P700
[-01] / P701
Pos: 576 /Anleitungen/ Elektronik/F U und Starter/6. Meldungen zu m Betriebszustand/Stör meldungen (Auflis tung)/Fehler E001 [ SK 180E/SK 2xxE/SK 5xxE/SK2xxE-FDS/SK 500P] @ 2\mod_1347452921592_388. docx @ 46427 @ @ 1
E001
1.0 Overtemp. Inverter
"Inverter overtemperature"
(inverter heat sink)
Inverter temperature monitoring
measurements are outside of the permissible temperature
range, i.e. the error is triggered if the permissible lower limit
is undershot or the permissible upper temperature limit is
exceeded.
Depending on the cause: Reduce or increase the
ambient temperature
Check the FI fan / control cabinet ventilation
Check the FI for dirt
1.1 Overtemp. FI internal
"Internal FI overtemperature"
(interior of FI)
Pos: 577 /Anleitungen/ Elektronik/F U und Starter/6. Meldungen zu m Betriebszustand/Stör meldungen (Auflis tung)/Fehler E002 [ SK 180E/SK 2xxE/SK 5xxE/SK2xxE- FDS] @ 2\mod_13474533021 52_388.docx @ 46451 @ @ 1
E002
2.0 Overtemp. Motor PTC
"Overtemperature motor
thermistor "
Motor temperature sensor (PTC) has triggered
Reduce motor load
Increase motor speed
Use external motor fan
2.1 Overtemp. Motor I²t
"Motor overtemperature I²t"
Only if I
2
t motor (P535) is
programmed.
I
2
t motor has triggered (calculated overtemperature of
motor)
Reduce motor load
Increase motor speed
2.2 Overtemp. Brake r.ext
"Overtemperature of external
brake resistor "
Overtemperature via digital
input (P420 […])={13}
Temperature monitor (e.g. brake resistor) has activated
Digital input is Low
Check connection, temperature sensor
Pos: 578 /Anleitungen/ Elektronik/F U und Starter/6. Meldungen zu m Betriebszustand/Stör meldungen (Auflis tung)/Fehler E003 [ SK 180E/SK 2xxE/SK 5xxE/SK2xxE-FDS] @ 2\mod_1347453 304788_388.doc x @ 46476 @ @ 1
E003
3.0 I
2
t overcurrent limit
a.c. inverter: I
2
t limit has triggered, e.g. > 1.5 x I
n
for 60s
(also note P504)
Continuous overload at inverter output
Possible encoder fault (resolution, defect,
connection)
3.1 Chopper overtemperature I
2
t
Brake chopper: I
2
t limit has activated, 1.5 times values
reached for 60s (please also pay attention to P554, if
present, and P555, P556, P557)
Avoid overcurrent in brake resistance
3.2 IGBT overcurrent
125% monitoring
De-rating (power reduction)
125% overcurrent for 50ms
Brake chopper current too high
for fan drives: enable flying start circuit (P520)
3.3 IGBT overcurrent fast
150% monitoring
De-rating (power reduction)
150% overcurrent
Brake chopper current too high
Pos: 579 /Anleitungen/ Elektronik/F U und Starter/6. Meldungen zu m Betriebszustand/Stör meldungen (Auflis tung)/Fehler E004 [ SK 2xxE-FDS/SK 500P] @ 12\mod_ 1467358136909_388. docx @ 335864 @ @ 1