6 Operating status messages
BU 0250 en-3021 167
E004
4.0 Overcurrent module
Error signal from module (short duration)
Short-circuit or earthing fault at FI output
Motor cable is too long
Use external output choke
Brake resistor faulty or resistance too low
Do not switch off P537!
The occurrence of a fault can significantly shorten the
service life of the device, or even destroy it.
4.1 Overcurrent measurement
"Overcurrent measurement"
P537 (pulse current switch-off) was reached 3x within 50 ms
(only possible if P112 and P536 are disabled)
FI is overloaded
Drive sluggish, insufficiently sized,
Ramps (P102/P103) too steep → Increase ramp time
Check motor data (P201 … P209)
4.5 Overcurrent / short circuit in
the brake rectifier
Overcurrent / short circuit in the
brake rectifier
Electromechanical brake defective
Electromechanical brake connected with
impermissible electrical data
Check the connection data
Pos: 580 /Anleitungen/ Elektronik/F U und Starter/6. Meldungen zu m Betriebszustand/Stör meldungen (Auflis tung)/Fehler E005 [ SK 180E/SK 2xxE/SK 5xxE/SK2xxE-FDS/SK 500 P] @ 2\mod_1347453309234_38 8.docx @ 46526 @ @ 1
E005
5.0
Overvoltage Ud
Link circuit voltage too high
• Increase deceleration time (P103)
Possibly set shutdown mode (P108) with delay (not
for lifting equipment)
Extend the quick stop time (P426)
Speed fluctuation (for example due to high inertia
loads) if necessary set the <U/f characteristic
curve (P211, P212)
FIs with brake chopper:
Dissipate energy feedback with a braking resistor
Check the function of the braking resistor (cable
break)
Resistance of connected braking resistor too high
5.1
Mains high voltage
Mains voltage too high
See Technical Data ( Section 7)
Pos: 581 /Anleitungen/ Elektronik/F U und Starter/6. Meldungen zu m Betriebszustand/Stör meldungen (Auflis tung)/Fehler E006 [ SK 5xxE, SK 2xxE, SK 2xxE-FDS/SK 500P] @ 2\mod_1361458416 246_388.docx @ 58807 @ @ 1
E006
6.0
Charging fault
Link circuit voltage too low
Mains voltage too low
See Technical Data ( Section 7)
6.1
Mains low voltage
Mains voltage too low
See Technical Data ( Section 7)
Pos: 582 /Anleitungen/ Elektronik/F U und Starter/6. Meldungen zu m Betriebszustand/Stör meldungen (Auflis tung)/Fehler E007 [ SK 500P, SK 180E, SK 200E(-FDS) , SK500E] @ 26\mod_1547550446 398_388.docx @ 2482096 @ @ 1
E007
7.0
Mains phase error
Error at terminal connection side
A mains phase is not connected
Mains asymmetrical
7.1
UZW phase error
Mains phase error
Pos: 583 /Anleitungen/ Elektronik/F U und Starter/6. Meldungen zu m Betriebszustand/Stör meldungen (Auflis tung)/Fehler E008 [ SK 180E, SK2xxE-FDS] @ 2\mod_13615203664 14_388.docx @ 58941 @ @ 1
E008
8.0 Parameter loss
(maximum EEPROM value
exceeded)
Error in EEPROM data
Software version of the stored data set not
compatible with the software version of the FI.
NOTE: Faulty parameters are automatically reloaded
(default data).
EMC interferences (see also E020)
8.1 Inverter type incorrect
EEPROM faulty
8.2 Reserved