6 Operating status messages
BU 0250 en-3021 167
E004
4.0 Overcurrent module
Error signal from module (short duration)
• Short-circuit or earthing fault at FI output
• Motor cable is too long
• Use external output choke
• Brake resistor faulty or resistance too low
Do not switch off P537!
The occurrence of a fault can significantly shorten the
service life of the device, or even destroy it.
4.1 Overcurrent measurement
"Overcurrent measurement"
P537 (pulse current switch-off) was reached 3x within 50 ms
(only possible if P112 and P536 are disabled)
• FI is overloaded
• Drive sluggish, insufficiently sized,
• Ramps (P102/P103) too steep → Increase ramp time
• Check motor data (P201 … P209)
4.5 Overcurrent / short circuit in
the brake rectifier
Overcurrent / short circuit in the
brake rectifier
• Electromechanical brake defective
• Electromechanical brake connected with
impermissible electrical data
Check the connection data
Pos: 580 /Anleitungen/ Elektronik/F U und Starter/6. Meldungen zu m Betriebszustand/Stör meldungen (Auflis tung)/Fehler E005 [ SK 180E/SK 2xxE/SK 5xxE/SK2xxE-FDS/SK 500 P] @ 2\mod_1347453309234_38 8.docx @ 46526 @ @ 1
Link circuit voltage too high
• Increase deceleration time (P103)
• Possibly set shutdown mode (P108) with delay (not
for lifting equipment)
• Extend the quick stop time (P426)
• Speed fluctuation (for example due to high inertia
loads) if necessary set the <U/f characteristic
curve (P211, P212)
FIs with brake chopper:
• Dissipate energy feedback with a braking resistor
• Check the function of the braking resistor (cable
break)
• Resistance of connected braking resistor too high
• See Technical Data ( Section 7)
Pos: 581 /Anleitungen/ Elektronik/F U und Starter/6. Meldungen zu m Betriebszustand/Stör meldungen (Auflis tung)/Fehler E006 [ SK 5xxE, SK 2xxE, SK 2xxE-FDS/SK 500P] @ 2\mod_1361458416 246_388.docx @ 58807 @ @ 1
Link circuit voltage too low
• Mains voltage too low
• See Technical Data ( Section 7)
• See Technical Data ( Section 7)
Pos: 582 /Anleitungen/ Elektronik/F U und Starter/6. Meldungen zu m Betriebszustand/Stör meldungen (Auflis tung)/Fehler E007 [ SK 500P, SK 180E, SK 200E(-FDS) , SK500E] @ 26\mod_1547550446 398_388.docx @ 2482096 @ @ 1
Error at terminal connection side
• A mains phase is not connected
• Mains asymmetrical
Pos: 583 /Anleitungen/ Elektronik/F U und Starter/6. Meldungen zu m Betriebszustand/Stör meldungen (Auflis tung)/Fehler E008 [ SK 180E, SK2xxE-FDS] @ 2\mod_13615203664 14_388.docx @ 58941 @ @ 1
E008
8.0 Parameter loss
(maximum EEPROM value
exceeded)
Error in EEPROM data
• Software version of the stored data set not
compatible with the software version of the FI.
NOTE: Faulty parameters are automatically reloaded
(default data).
• EMC interferences (see also E020)
8.1 Inverter type incorrect
• EEPROM faulty
8.2 Reserved