8.3 EEPROM KSE error
(Customer unit incorrectly
identified (customer’s interface
equipment))
The upgrade level of the frequency inverter was not
correctly identified.
• Switch mains voltage off and on again.
8.4 Internal EEPROM error
(Database version incorrect)
8.7 EEPR copy not the same
Pos: 584 /Anleitungen/ Elektronik/F U und Starter/6. Meldungen zu m Betriebszustand/Stör meldungen (Auflis tung)/Fehler E009 "r eserviert" [SK 180E/SK 2xxE/SK2xxE-FDS] @ 2\mod_134 7453797027_388.doc x @ 46701 @ @ 1
E009
--- Reserved
Pos: 585 /Anleitungen/ Elektronik/F U und Starter/6. Meldungen zu m Betriebszustand/Stör meldungen (Auflis tung)/Fehler E010 [ SK 180E/SK 2xxE/SK2xxE-FDS] @ 40\mod_15759659 68975_388.doc x @ 2581250 @ @ 1
E010
10.0 Bus Timeout
Telegram time-out / Bus off 24V int. CANbus
• Data transfer is faulty. Check P513.
• Check physical bus connections
• Check bus protocol program process.
• Check Bus Master.
• Check 24V supply of internal CAN/CANopen Bus.
• Node guarding error (internal CANopen)
• Bus Off error (internal CANbus)
10.2 Bus Timeout Option
Telegram timeout
• Telegram transfer is faulty.
• Check physical bus connections
• Check bus protocol program process.
• Check Bus Master.
• PLC is in the "STOP" or "ERROR" state.
10.4 Init error Option
Initialisation error in bus module
• Check Bus module current supply.
• DIP switch setting of a connected I/O extension
module is incorrect
10.1 System error option
System error bus module
• Further details can be found in the respective
additional bus instructions.
I/O extension:
• Incorrect measurement of the input voltage or
undefined provision of the output voltage due to error
in reference voltage generation.
• Short circuit at analogue output
10.3
10.5
10.6
10.7
10.9 Module missing / P120
The module entered in parameter (P120) is not available.
• Check connections
Pos: 586 /Anleitungen/ Elektronik/F U und Starter/6. Meldungen zu m Betriebszustand/Stör meldungen (Auflis tung)/Fehler E011 [ SK 180E ... SK 5xxE/SK 500P/SK 30 0P] @ 43\mod_15923865767 74_388.docx @ 2634700 @ @ 1
Internal control terminal (internal data bus) incorrect or
interference due to radio radiation (EMC).
• Check control connections for short circuit.
• Minimise EMC interferences by separate routing of
control and power cables.
• Earth devices and shields well.
Pos: 587 /Anleitungen/ Elektronik/F U und Starter/6. Meldungen zu m Betriebszustand/Stör meldungen (Auflis tung)/Fehler E012 [ SK 180E/SK 2xxE/SK2xxE-FDS/ SK 500P] @ 2\mod_1347454267926_3 88.docx @ 46726 @ @ 1
E012
12.0 External watchdog
The Watchdog function is selected at a digital input and the
impulse at the corresponding digital input is not present for
longer than the time set in parameter P460 >Watchdog
time<.
• Check connections
• Check setting P460