NORDAC LINK (SK 250E-FDS ... SK 280E-FDS) Users Manual for Frequency Inverters as Field Distributors
168 BU 0250 en-3021
8.3 EEPROM KSE error
(Customer unit incorrectly
identified (customer’s interface
equipment))
The upgrade level of the frequency inverter was not
correctly identified.
Switch mains voltage off and on again.
8.4 Internal EEPROM error
(Database version incorrect)
8.7 EEPR copy not the same
Pos: 584 /Anleitungen/ Elektronik/F U und Starter/6. Meldungen zu m Betriebszustand/Stör meldungen (Auflis tung)/Fehler E009 "r eserviert" [SK 180E/SK 2xxE/SK2xxE-FDS] @ 2\mod_134 7453797027_388.doc x @ 46701 @ @ 1
E009
--- Reserved
Pos: 585 /Anleitungen/ Elektronik/F U und Starter/6. Meldungen zu m Betriebszustand/Stör meldungen (Auflis tung)/Fehler E010 [ SK 180E/SK 2xxE/SK2xxE-FDS] @ 40\mod_15759659 68975_388.doc x @ 2581250 @ @ 1
E010
10.0 Bus Timeout
Telegram time-out / Bus off 24V int. CANbus
Data transfer is faulty. Check P513.
Check physical bus connections
Check bus protocol program process.
Check Bus Master.
Check 24V supply of internal CAN/CANopen Bus.
Node guarding error (internal CANopen)
Bus Off error (internal CANbus)
10.2 Bus Timeout Option
Telegram timeout
Telegram transfer is faulty.
Check physical bus connections
Check bus protocol program process.
Check Bus Master.
PLC is in the "STOP" or "ERROR" state.
10.4 Init error Option
Initialisation error in bus module
Check Bus module current supply.
DIP switch setting of a connected I/O extension
module is incorrect
10.1 System error option
System error bus module
Further details can be found in the respective
additional bus instructions.
I/O extension:
Incorrect measurement of the input voltage or
undefined provision of the output voltage due to error
in reference voltage generation.
Short circuit at analogue output
10.3
10.5
10.6
10.7
10.9 Module missing / P120
The module entered in parameter (P120) is not available.
Check connections
Pos: 586 /Anleitungen/ Elektronik/F U und Starter/6. Meldungen zu m Betriebszustand/Stör meldungen (Auflis tung)/Fehler E011 [ SK 180E ... SK 5xxE/SK 500P/SK 30 0P] @ 43\mod_15923865767 74_388.docx @ 2634700 @ @ 1
E011
11.0
Customer terminal
A/D converter error
Internal control terminal (internal data bus) incorrect or
interference due to radio radiation (EMC).
Check control connections for short circuit.
Minimise EMC interferences by separate routing of
control and power cables.
Earth devices and shields well.
Pos: 587 /Anleitungen/ Elektronik/F U und Starter/6. Meldungen zu m Betriebszustand/Stör meldungen (Auflis tung)/Fehler E012 [ SK 180E/SK 2xxE/SK2xxE-FDS/ SK 500P] @ 2\mod_1347454267926_3 88.docx @ 46726 @ @ 1
E012
12.0 External watchdog
The Watchdog function is selected at a digital input and the
impulse at the corresponding digital input is not present for
longer than the time set in parameter P460 >Watchdog
time<.
Check connections
Check setting P460