5 Parameter
BU 0250 en-3021 93
Pos: 266 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ P2xx Motordaten / Kennli nienparameter @ 0\ mod_1327588046860_388.d ocx @ 7838 @ 3 @ 1
5.2.3 Motor data / Characteristic curve parameters
Parameter
{factory setting}
Setting value / Description / Note Supervisor Parameter set
Pos: 267 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P200- P299/Parameter P200 – Motor liste - Allgemeiner Teil [BU0180, BU0200, BU 0500, SK 2xxE-FDS] @ 41\mod_15864 29779497_388.doc x @ 2600932 @ @ 1
P200
Motor list
(Motor list)
P
{ 0 }
The factory settings for the motor data can be edited with this parameter. A 4-pole IE1 three-phase
standard motor with the FI rated power is set at the factory in parameters P201 … P209.
By selecting one of the possible digits and pressing the ENTER key, all of the motor parameters
(P201 … P209) are set to the selected standard power. The motor data is based on a 4-pole three-
phase standard motor. The motor data for NORD IE4 motors can be found in the final section of the
list.
As P200 is = 0 again after input acknowledgement, the set motor can be controlled via the
parameter P205.
If IE2/IE3 motors are used, after selecting an IE1 motor (P200), the motor data in P201 … P209
must be adapted to the data on the motor type plate.
Pos: 268 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P200- P299/Parameter P200 – Motor liste [SK 2xxE-FDS] @ 12\mod_1468418308713_3 88.docx @ 338805 @ @ 1
No motor: In this setting, the FI operates without current control, slip compensation and
pre-magnetising time, and is therefore not recommended for motor applications. Possible
applications are induction furnaces or other applications with coils and transformers. In
this case, the following motor data are set: 50.0 Hz / 1500 rpm / 15.0 A / 400 V /
ϕ
Ω
2 = 0.25kW 230V 18 = 1.1 kW 230V 34 = 4.0 kW 400V 95 = 0.75kW 230V 80T1/4
6 = 0.37kW 230V 22 = 1.5 kW 230V 38 = 5.5 kW 400V 99 = 1.50kW 230V 90T3/4
Reserved,
do not use