NORDAC LINK (SK 250E-FDS ... SK 280E-FDS) Users Manual for Frequency Inverters as Field Distributors
94 BU 0250 en-3021
Pos: 270 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P200- P299/Parameter P201 Motor Nennfrequenz @ 41\mod_158 6432457133_388.doc x @ 2600968 @ @ 1
P201
Nominal frequency
(Nominal frequency)
S P
10.0 … 399.9 Hz
{ see information }
The motor frequency determines the V/f break point at which the FI supplies the nominal voltage
(P204) at the output.
Default setting
The default setting depends on the nominal power of the FI and the setting in P200.
Pos: 271 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P200- P299/Parameter P202 Motor Nenndrehzahl @ 41\mod_15864 32759437_388.doc x @ 2601004 @ @ 1
P202
Nominal speed
(Nominal speed)
S P
150 … 24000 rpm
{ see information }
The nominal motor speed is important for correct calculation and control of the motor slip and the
speed display (P001 = 1).
Information
Default setting
The default setting depends on the nominal power of the FI and the setting in P200.
Pos: 272 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P200-P299/Parameter P203 Motor Nennstr om @ 41\mod_158643305329 0_388.docx @ 2601040 @ @ 1
P203
Nominal current
(Nominal current)
S P
0.1 … 1000.0 A
{ see information }
The nominal motor current is a decisive parameter for current vector control.
Information
Default setting
The default setting depends on the nominal power of the FI and the setting in P200.
Pos: 273 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P200-P299/Parameter P204 Motor Nennsp annung @ 41\mod_1586433246 488_388.docx @ 2601076 @ @ 1
P204
Nominal voltage
(Nominal voltage)
S P
100 … 800 V
{ see information }
The nominal voltage matches the mains voltage to the motor voltage. In combination with the
nominal frequency, the voltage/frequency characteristic curve is produced.
Default setting
The default setting depends on the nominal power of the FI and the setting in P200.
Pos: 274 /Anleitun gen/Elektronik/F U und Starter/5. Parameter /Parameterauflis tung (P000 ...)/ P200-P299/Parameter P205 Motor Nennleistung @ 41\mod_15 86433362067_388.d ocx @ 2601112 @ @ 1
P205
Nominal power
(Nominal power)
P
0.00 … 250.00 kW
{ see information }
The motor nominal power controls the motor set via P200.
Default setting
The default setting depends on the nominal power of the FI and the setting in P200.