6 Operating status messages
BU 0250 en-3021 175
3.0
Pos: 624 /Anleitungen/ Elektronik/F U und Starter/6. Meldungen zu m Betriebszustand/Betr iebsstörungen ( Auflistung)/FAQ Betri ebsstörungen_09 [SK 1x0E, SK 2xxE, SK 2xxE-FDS] @ 9\ mod_1448963460429_388.d ocx @ 268605 @ @ 1
Intermittent communication
error between FI and option
modules
System bus terminating resistor not set
Poor connection contacting
Interference on system bus line
Maximum system bus length exceeded
First and last subscriber only:
Set DIP switches for
terminating resistance
Check connections
Connect GND of all FI
connected to system bus
Pay attention to routing
regulations (separate routing
of signal and control cables
and mains and motor cables)
Check cable lengths (system
bus)
Pos: 625 /Anleitungen/ Elektronik/F U und Starter/6. Meldungen zu m Betriebszustand/Betr iebsstörungen ( Auflistung)/FAQ Betr iebsstörungen_10_ Tabellenuntersc hrift [SK 1xxE, SK 2xxE, SK xxxE-FDS] @ 9\mod_1448963453684_ 388.docx @ 268572 @ @ 1
Table 5: FAQ operational problems