NORDAC LINK (SK 250E-FDS ... SK 280E-FDS) – Users Manual for Frequency Inverters as Field Distributors
178 BU 0250 en-3021
Pos: 630 /Anleitungen/ Elektronik/F U und Starter/7. Technische Da ten/Elektrisc he Daten_Einleitung [SK xxxE -FDS] @ 12\mod_146736234 0032_388.docx @ 335899 @ 2 @ 1
7.3 Electrical data
The following tables contain the data which is relevant for UL.
Details of the UL/CSA approval conditions can be found in Section 1.6.1 "UL and CSA approval". Use
of mains fuses which are faster than those stated is permissible.
Pos: 631 /Anleitungen/ Elektronik/F U und Starter/7. Technische Da ten/Elektrisc he Daten [SK 1xxE, SK 2xxE, SK xxxE-FDS ]/Elektrische Da ten 3~ 400V [SK 2xxE-FDS] @ 50\mod_1600933499782_388. docx @ 2672841 @ 3 @ 1
7.3.1 Electrical data 3~400 V
Device type SK 2xxE-FDS-…
-370-340- -550-340- -750-340- -111-340- -151-340-
0 0 0 1 1
Nominal motor power
(4-pole standard motor)
400 V
Mains voltage
3 AC 380 … 500 V, - 20 % / + 10 %, 47 … 63 Hz
Input current
rms
1)
2)
Output current
rms
1)
FLA
2)
Min. brake resistance Accessories
Ω
Ω
Ω
Ω
Ω
Max. continuous power / max. continuous current
General fuses (AC) (recommended)
UL fuses (AC) – permitted
X
6)
1) Note the derating curve ( Section 8.4.4 "Reduced output current due to low voltage").
2) FLA – Full Load Current, maximum current for the entire mains voltage range as stated above (380 V – 500 V) according to UL/CSA
3) Only with "Fan" (standard equipment)
4) for group fuses: maximum fuse size: 30 A
5) Maximum mains short-circuit current, Note: Further restrictions are possible depending on the plug connector which is used (
Section 1.6.1
"UL and CSA approval")
6) "inverse time trip type" according to UL 489