Technical AS-Interface data
Designation
Option slot M8: Device with connector option …
… “-ASI” … “-ASS” … “-AUX” … “-AXS”
(yellow cable)
≤ 500 mA
1)
≤ 25 mA
2)
(black cable)
Connection not possible
≤ 800 mA
Extended required master M4
M3, M4
M4
M3, M4
1st slave 2nd slave - 1st slave 2nd slave -
Number of application data
(BUS I/O)
From the point of view of
the AS-i master
4I/4O 2I/1O
3)
4I/4O 4I/4O 2I/1O
3)
4I/4O
From the point of view of
SK 2xxE-FDS
4I/4O 1I/2O
3)
4I/4O 4I/4O 1I/2O
3)
4I/4O
For power supply exclusively via the yellow AS-i cable
2)
For the power supply to the inverter and any connected sensors or actuators via the integrated mains unit of the FI (Option "-HVS") and/or
via the black cable.
+ extended data transfer according to the CTT2 protocol (parameter data, process data)
Pos: 191 /Anleitungen/ Elektronik/F U und Starter/4. Inbetriebna hme/AS-Interfac e [alle Geräte]/Busaufb au und Topologie_01 [ SK 1xxE, SK 2xxE, SK xxxE-FDS] @ 41\mod_15 83920379238_388.d ocx @ 2596684 @ 3 @ 1
4.5.3 Bus structure and topology
The AS-Interface network structure is optional (line, star, ring and tree structure) and is managed by
an AS-Interface master as an interface between PLC and slaves. An existing network can be
extended with further slaves up to a limit of 31 standard slaves or 62 slaves in the extended
addressing mode. The addressing of slaves is done by the master or a respective addressing unit.
An AS-i master communicates independently and exchanges data with the connected AS-i slaves. No
standard power supply units must be used in the AS-Interface network. For each AS-Interface line,
only one special AS-Interface power supply unit may be used for voltage supply. This AS-Interface
voltage supply is connected directly to the yellow standard cable (AS-i(+) and AS-i(-) cable) and
should be positioned as close as possible to the AS-i master to keep the voltage drop low.
To avoid interferences, the PE connection of the AS-Interface power supply unit (if available)
must be earthed.
The brown AS-i(+) and the blue AS-i(-) wire of the yellow AS-Interface cable must not be earthed.