6 Operating status messages
BU 0250 en-3021 169
12.1 Limit moto./Customer
"Drive switch-off limit"
The drive switch-off limit (P534 [-01]) has triggered.
Reduce load on motor
Set higher value in (P534 [-01]).
12.2 Limit gen.
"Generator switch-off limit"
The generator switch-off limit (P534 [-02]) has triggered.
Reduce load on motor
Set higher value in (P534 [-02]).
12.3 Torque limit
Limit from potentiometer or setpoint source has switched off.
P400 = 12
12.4 Current limit
Limit from potentiometer or setpoint source has switched off.
P400 = 14
12.5 Load monitor
Switch-off due to overshooting or undershooting of
permissible load torques ((P525) … (P529)) for the time set
in (P528).
Adjust load.
Change limit values ((P525) ... (P527)).
Increase delay time (P528).
Change monitoring mode (P529).
12.8 AI minimum
„Analogue In minimum“
Switch-off due to undershooting of the 0% adjustment value
(P402) with setting (P401) "0-10V with switch-off on error 1"
or "....2"
12.9 AI maximum
„Analogue In maximum
Switch-off due to overshooting of the 100% adjustment
value (P402) with setting (P401) "0-10V with switch-off on
error 1" or "....2"
Pos: 588 /Anleitungen/ Elektronik/F U und Starter/6. Meldungen zu m Betriebszustand/Stör meldungen (Auflis tung)/Fehler E013 [ SK 200E ... SK 5xxE] @ 2\mod_13474542712 18_388.docx @ 46751 @ @ 1
E013
13.0 Encoder error
No signal from encoder
Check 5V sensor if present.
Check supply voltage of encoder.
13.1 Speed slip error
"Speed slip error"
The slip speed error limit was reached.
Increase setting in P327.
13.2 Shut-down monitoring
The slip error monitoring has triggered; the motor could not
follow the setpoint.
Check motor data P201-P209! (Important for the
current controller)
Check motor circuit.
In servo mode, check the encoder setting P300 and
check the following
Increase setting value for torque limit in P112.
Increase setting value for current limit in P536.
Check deceleration time P103 and extend if
necessary
13.5 Reserved
Error message for POSICON see supplementary
instructions
13.6 Reserved
Error message for POSICON see supplementary
instructions
Pos: 589 /Anleitungen/ Elektronik/F U und Starter/6. Meldungen zu m Betriebszustand/Stör meldungen (Auflis tung)/Fehler E014 "r eserviert" [SK 200E ... SK 5xxE/SK 500P] @ 2\mod_134 7454273854_388.doc x @ 46776 @ @ 1
E014
--- Reserved
Error message for POSICON see supplementary
instructions
Pos: 590 /Anleitungen/ Elektronik/F U und Starter/6. Meldungen zu m Betriebszustand/Stör meldungen (Auflis tung)/Fehler E015 [ SK 180E ... SK 5xxE] @ 2\mod_1347454278051_3 88.docx @ 46801 @ @ 1
E015
--- Reserved
Pos: 591 /Anleitungen/ Elektronik/F U und Starter/6. Meldungen zu m Betriebszustand/Stör meldungen (Auflis tung)/Fehler E016 [ SK 135E ... SK 5xxE, SK xxxE-FDS] @ 2\mod_13474542806 25_388.docx @ 46826 @ @ 1
E016
16.0 Motor phase error
A motor phase is not connected.
Check P539
Check motor connection