NORDAC LINK (SK 250E-FDS ... SK 280E-FDS) Users Manual for Frequency Inverters as Field Distributors
162 BU 0250 en-3021
Pos: 548 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P700- P799/Parameter P747 – Umric hterspannungsbereic h [SK 1x0E, SK 2xxE, SK 2xxE-FDS] @ 9\mod_1448457030116_388. docx @ 266976 @ @ 1
P747 Inverter Volt. Range
(Inverter voltage range)
0 ... 2
Indicates the mains voltage range for which this device is specified.
0 = 100...120V
1 = 200...240V
2 = 380...480V
Pos: 549 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P700- P799/Parameter P748 Statu s CANopen [SK 1x0E, SK 2xxE, SK 2xxE-FDS] @ 2\mod_13469322101 80_388.docx @ 43680 @ @ 1
P748
CANopen status
(CANopen status (system bus status))
0000 ... FFFF (hex)
or
0 ... 65535 (dec)
Shows the status of the system bus.
Bit 0:
Bit 1:
Bit 2:
Bit 3:
Bit 4:
Bit 5:
Bit 6:
Bit 7:
Bit 8:
Bit 9:
Bit 10:
24V Bus supply voltage
CANbus in "Bus Warning" status
CANbus in "Bus Off" status
System bus Bus module online (field bus module, e.g.: SK xU4-PBR)
System bus Additional module 1 online (I/O - module, e.g.: SK xU4-IOE)
System bus Additional module 2 online (I/O - module, e.g.: SK xU4-IOE)
The protocol of the CAN module is 0 = CAN / 1 = CANopen
Vacant
"Bootup Message" sent
CANopen NMT State
CANopen NMT State
CANopen NMT State Bit 10 Bit 9
Stopped
Pre- Operational
Operational
0
0
1
0
1
0
Pos: 550 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P700- P799/Parameter P749 Zus tand DIP-Schalter [SK 2 xxE-FDS] @ 12\ mod_1467356772183_388. docx @ 335795 @ @ 1
P749
Status of DIP switches
(Status of DIP switches)
0000 ... 01FF (hex)
or
0 ... 511
(dec)
This parameter indicates the various internal configurations.
Bit 0:
Bit 1:
System bus address (Bit 0)
System bus address (Bit 1)
Address
Bit 1
Bit 0
32
0
0
34
0
1
36 1 0
38
1
1
Bit 2:
Bit 3 6:
Bit 7:
Bit 8:
System bus active
Reserved
Internal brake resistor
EEPROM (Memory Module)
Bit 8 = 0: plugged in / Bit 8 = 1: not plugged in
Pos: 551 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P700- P799/Parameter P750 Sta tistik Übe rstrom @ 0\mod_1 328178425687_388. docx @ 13566 @ @ 1
P750
Stat. overcurrent
(Overcurrent statistics)
S
0 ... 9999 Number of overcurrent messages during the operating period P714.
Pos: 552 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P700- P799/Parameter P751 Sta tistik Überspannung @ 0\mod_1328178489671_388. docx @ 13589 @ @ 1
P751
Stat. Overvoltage
(Overvoltage statistics))
S
0 ... 9999 Number of overvoltage messages during the operating period P714.