NORDAC LINK (SK 250E-FDS ... SK 280E-FDS) Users Manual for Frequency Inverters as Field Distributors
38 BU 0250 en-3021
Pos: 82 /Anleitungen/ Elektronik/FU und St arter/2. Montage und Inst allation/Montage/ FDS [SK xxxE-FDS]/Auss tattungsvarian ten_03_Konfiguration der Optionsplätze der Anschlussebene_04 [SK 2 xxE-FDS] @ 11\mod_1465465471 437_388.docx @ 328420 @ 5 @ 1
Area 2, option slots Z1 to Z4
The option slots M1 to M8 are designed for M12 plug connectors. No fixed functions are allocated to
the option slots. Primarily, these option slots are used to connect initiators, an integrated option of type
SK CU4-… . However, if required they can also accept plug connectors for connecting other signal
and control cables. The mating plug connector is not included in the scope of supply.
As the built-in plug connector cannot be adjusted during assembly, the use of angled cable plug
connectors is not recommended.
Pos: 83 /Anleitungen/ Elektronik/FU und St arter/2. Montage und Inst allation/Monta ge/FDS [SK xxxE-FDS]/Stec kerbelegung M12-Steckverbi nder_03 [SK 2xxE-FDS] @ 38\mod_156 9236175313_388.doc x @ 2560597 @ @ 1
Function Plug connector
1)
Option slot
2)
Contact
diagram
Contact assignments
1
2
3
4
5
No.
Colour
DIN1 / DIN2
Socket,
A-coded
24 V
DIN2
GND
DIN1
PE
Z3
black
DIN1
24 V
GND
DIN1
PE
Z3
black
DIN2
24 V
GND
DIN2
PE
Z4
black
AIN1 / AIN2
24 V
AIN2
GND
AIN1
+10 V
Ref
Z1
white
AIN2
24 V
AIN2
GND
+10 V
Ref
Z2
white
AOUT
24 V
AIN2
GND
+10 V
Ref
Z1 - Z4
white
24VO
24 V
GND
Z1 - Z4
black
CAO
(Bus-IN)
Schield
24 V
GND
CAN_H
CAN_L
Z1
gr
DEV
(Bus-IN)
Schield
24 V
GND
CAN_H
CAN_L
Z1
gr
CAO-OUT
(Bus-OUT)
Plug connectors,
A-coded
24 V
GND
CAN_H
CAN_L
Z2
gr
24VI
24 V
GND
Z1 - Z4
black
ETH
(Bus-IN)
Socket,
D-coded
TX+
RX+
TX-
RX-
Z1
green
ETH
(Bus-OUT)
TX+
RX+
TX-
RX-
Z2
green
PBR
(Bus-IN)
Plug connectors,
B-coded
PBR A
PBR B
Z1 / Z2
violet
PBR
(Bus-OUT)
Socket,
B-coded
5 V
PBR A
GND
PBR B
Z2 / Z1
violet
1)
The housing of the plug connectors are internally wired to PE.
2)
If 2 SK CU4-IOE modules are installed, or if an IO module is installed together with an SK CU4-… field bus module, the initiators and
actuators are output via any of the option slots Z1 to Z4. (For detailed information refer to the order confirmation.)
Pos: 85 /Anleitungen/ Elektronik/FU und St arter/2. Montage und Inst allation/Montage/ FDS [SK xxxE-FDS]/Stec kerbelegung M12-Steckverbi nder_04 [SK 2xxE-FDS] @ 38\mod_156 9240177538_388.doc x @ 2560633 @ @ 1