2 Assembly and installation
BU 0250 en-3021 47
Information
Response time of digital inputs
The response time of a digital signal is approx. 4 5 ms and consists of the following:
Scan time
1 ms
Signal stability check
3 ms
Internal processing
<
1 ms
Pos: 125 /Anleitungen/ Elektronik/F U und Starter/1. Allgemeine s/Sicherheits- und Installationshi nweise und Warn- Gefahrenhi nweise/neu/ Warn- und Gefahrenhinwei se/Information - K abelführung @ 29\mod_155204 5826996_388.docx @ 2502 107 @ @ 1
Cable laying
All control cables (including thermistors) must be routed separately from the mains and the motor
cables to prevent interference in the device.
If the cables are routed in parallel, a minimum distance of 20 cm must be maintained from cables
which carry a voltage of > 60 V. The minimum distance may be reduced by screening the cables
which carry a voltage, or by the use of earthed metal partitions within the cable conduits.
Alternatively: Use a hybrid cable with shielding of the control lines.