5 Parameter
BU 0250 en-3021 89
Information
Torque limitation during active setpoint delay
(P107 / P114)
During an active setpoint delay, the torque is limited to a maximum of 160% of the rated
torque. This prevents the occurrence of excessive currents in the inverter or breakdown of the
motor if
For application of the brake, the brake reaction time (P107) is set too long.
For release of the brake, the value for the absolute minimum frequency (P505) is set too
high.
Pos: 256 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P100- P199/Parameter P107 Ei nfallzeit Bremse_Beispi el @ 4\mod_1396519433556 _388.docx @ 123851 @ @ 1
Recommendation for applications:
Lifting equipment with brake, without speed feedback Lifting equipment with brake
P114 = 0.02...0.4 s *
P107 = 0.02...0.4 s *
P201…P208 = Motor data
P434 = 1 (ext. brake)
P505 = 2...4 Hz
for safe start-up
P112 = 401 (off)
P536 = 2.1 (off)
P537 = 150 %
P539 = 2/3 (I
SD
monitoring)
to prevent load drops
P214 = 50...100 % (precontrol)
* Settings (P107/114) depending on
brake type and motor size. At low power
levels (< 1.5
kW) lower values apply for
higher power ratings (> 4.0
kW) are
larger values.
Output
frequency
P107
Brake released
P114
or
P107, when P114 = 0
ON signal
P505
OFF signal
Time