Kronos Series 3
35
Figure 27: GNSS and out-of-bound limits settings
Description
GPS is always enabled and cannot be disabled.
GALILEO can be enabled or disabled as desired.
Either GLONASS or BeiDou can be enabled, but not both at the same time.
Table 15: GNSS settings
Description
When the time becomes inaccurate by more than the time specified value, the
LOWQUALITY alarm is set. The range is 0.001 to 4000ms.
Default: 0.5ms
When the time becomes inaccurate by more than the time specified value, the
BADTIME alarm is set. The range is 0.001 to 4000ms.
Default: 1000ms
Table 16: Out-of-bounds limits settings
See section Clock States for an explanation of how the limits in Table 16 affect clock operation.