Kronos Series 3
69
Appendix E – Sample Configuration File
# kronos series 3 configuration file
VERSION = 0091
# Passwords for configuration, status, logs and firmware upgrade, HTTPS
enforcement
# ENFORCE_HTTPS can be NEVER, CFG_ONLY or ALWAYS
[ACCESS]
STSPWD =
CFGPWD = novatech
FWPWD = novatech
ENFORCE_HTTPS = ALWAYS
# IDENTIFIER, LOCATION and CONTACT are shown on the dashboard web page and
# reported as sysName, sysLocation and sysContact when using SNMP
# Replace with values meaningful to the installation
[GENERAL]
IDENTIFIER = Kronos Series 3
LOCATION =
CONTACT =
# Timezone and daylight saving time rules
# In order to disable DST, specify DST_RULE = NONE
[TIMEZONE]
OFFSET = +06:00
STD_NAME = CST
DST_NAME = CDT
DST_RULE = US
DST_BEGIN = M3.2.0/2:00
DST_END = M11.1.0/2:00
# GNSS related settings
# ANT_DELAY is the antenna cable delay compensation in nanoseconds (~4 ns for
# each meter of coax cable)
# GALILEO, GLONASS and BEIDOU can be set to TRUE/FALSE in order to enable/disable
# the usage of additional constellations
# FAKEGNSS and FAKETIME can be used to simulate antenna connection and GNSS
# signal reception
# (use for commissioning work only, set to FALSE before normal operation !)
[GNSS]
ANT_DELAY = 60
GALILEO = TRUE
GLONASS = TRUE
BEIDOU = FALSE
FAKEGNSS = FALSE
FAKETIME = 2023-01-01 12:00
# User defined out-of-bounds limits (in miliseconds)
# Valid values are from 0.001 (1 microsecond) to 4000 (4 seconds)
[LIMITS]
LOWQUALITY = 0.5
BADTIME = 1000