Kronos Series 3
42
Parameter
Description
Time
UTC
Local
The output can be set to send either UTC time or local time.
POLARITY
Configures the polarity of the signal at OUTPUTn. Valid values are
NORMAL and INVERTED.
Default: NORMAL
Table 21: Output signals
5.6 Network Settings (Offline)
This section configures the network parameters for clock’s Ethernet ports. The clock has one RJ45 Ethernet
port and four SFP slots.
The same settings can be made in the webpage as described in Network Settings (Online).
# Network parameters
# (see reference manual for further details)
[NETWORK]
IPADDR_A = 10.0.0.150
IPMASK_A = 255.0.0.0
IPADDR_B =
IPMASK_B =
REDUNDANCY_B = NONE
GATEWAY = 10.0.0.2
CHANGEIP = TRUE
Item
Description
IPADDR_A
IPMASK_A
Enter the IP address and netmask for port A.
IPADDR_B
IPMASK_B
Enter the IP address and netmask for port B.
REDUNDANCY_B
NONE Port B does not use PRP/HSR.
PRP Port B uses PRP.
HSR Port B uses HSR.
GATEWAY
Enter the IP address of the gateway used by the clock.
CHANGEIP
TRUE Enable changing the IP address of port A via the rotary knob.
FALSE Disable changing the IP address of port A via the rotary knob.
See Change Using Front Rotary Knob for details.
Table 22: Network settings