EasyManua.ls Logo

Novatech Kronos 2 Series - NTP Settings (Offline); PTP Settings (Offline); Table 23: NTP and Strata Settings

Novatech Kronos 2 Series
72 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Kronos Series 3
43
5.7 NTP Settings (Offline)
This section configures the NTP (Network Time Protocol) settings. The same settings can be made in the
webpage as described in NTP Settings (Online).
# Settings for the Network Time Protocol
# Specify stratum to report when in HOLDOVER, LOWQUALITY and BADTIME states
[NTP]
ENABLE_A = TRUE
ENABLE_B = FALSE
STRATUM_HOLDOVER = 0
STRATUM_LOWQUALITY = 1
STRATUM_BADTIME = 11
Parameter
Description
[NTP]
Section name for NTP settings.
ENABLE_A
ENABLE_B
TRUE enables NTP for the respective port.
FALSE disables NTP for the respective port.
STRATUM_HOLDOVER
Stratum to be reported by the NTP service during HOLDOVER. Values
between 0 and 5 are accepted.
Default: 0
STRATUM_LOWQUALITY
Stratum to be reported by the NTP service during LOWQUALITY. Values
between 0 and 9 are accepted.
Default: 0
STRATUM_BADTIME
Stratum to be reported by the NTP service during BADTIME. Values between
0 and 14 are accepted.
Default: 0
Table 23: NTP and strata settings
5.8 PTP Settings (Offline)
This section configures PTP for ports B, C, and D. It is recommended to configure the PTP settings with
the webpage (PTP Settings (Online)) instead of in the configuration file since after the selecting the desired
profile, the webpage automatically populates all parameters with appropriate values. The actual name of
the profile selected in the webpage is not stored in the configuration.
# PTP Settings
[PTP]
ENABLE_B = TRUE
LAYER_B = L2
DOMAIN_B = 254
PRIORITY1_B = 128
PRIORITY2_B = 128
PATHDELAYMECHANISM_B = P2P
ANNOUNCEINTERVAL_B = 1
ANNOUNCETIMEOUT_B = 3
SYNCINTERVAL_B = 1

Table of Contents