Omron C200H - Block Set - Bset(71)

Omron C200H
374 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
135
0
0 0 0 0 111000100001
Bit
15
Bit
00
D
C
1101001001110001
D+1
0001101100100111
D+2
.
.
.
.
.
.
.
.
.
.
0111000110001010
D+15
1000001100000111
D+3
0 1 1
S
1
Bit
15
Bit
00
. . . . . .
.
.
.
Flags ER: The bit designator C is not BCD, or it is specifying a non-existent bit
(i.e., bit specification must be between 00 and 15).
Indirectly addressed DM word is non-existent. (Content of *DM word
is not BCD, or the DM area boundary has been exceeded.)
EQ: ON when the content of S is zero; otherwise OFF.
The following example shows how to use WTC(64) to move the contents of
word DM 0100 (00 to 15) to bit column 15 of the set (DM 0200 to DM 0215).
WTC(64)
DM 0100
DM 0200
#0015
00000
Address Instruction Operands
00000 LD 00000
00001 WTC(64)
DM 0100
DM 0200
# 0015
5-14-5 BLOCK SET – BSET(71)
S: Source data
IR, SR, AR, DM, HR, TC, LR, #
St: Starting word
IR, AR, DM, HR, TC, LR
Ladder Symbols
Operand Data Areas
E: End Word
IR, AR, DM, HR, TC, LR
BSET(71)
S
St
E
@BSET(71)
S
St
E
St must be less than or equal to E, and St and E must be in the same data
area.
When the execution condition is OFF, BSET(71) is not executed. When the
execution condition is ON, BSET(71) copies the content of S to all words
from St through E.
Example
Limitations
Description
Data Movement Section 5-14