CHAPTER 4 APPLIED OPERATION
E5CK
4–18
Ă There is no order of priority in event input, key operations and commuĆ
nications command setup. However, remote/local, auto/manual, hold/
hold cancel or pattern selection be set to either of ON or OFF. So, paramĆ
eters will always follow event input even if you try to switch settings by
key operation and communications commands.
Ă Program operation is stopped (reset) at the rising edge (OFF
³ON) of
the event input signal, and the RST LED lights. Program operation is
started (run) at the falling edge (ON
³OFF) of the event input signal.
Ă When event input is set to ON", the controller is switched to manual
operation, and the MANU" LED lights.
Ă This function is enabled only during program operation.
Ă The program is paused (Hold) when the event input is ON, and the
HOLD" LED lights. Holds continue until the state of the event input
changes to OFF.
Ă This function is enabled only during program operation.
Ă Program steps are advanced at the rising (OFF³ON) edge of the event
input signal. Accordingly, be sure to set event input OFF before you use
this function.
Ă This function is enabled only when the program is reset.
Ă Patterns are selected by pattern select input. The number of patterns
that can be selected are dependent on the value set to the number of patĆ
terns" parameter. For example, when this parameter is set to 4", you
can select from patterns 0 or 2.
Symbol Parameter Name: Mode Description
Event input assignments Option
Event input functions
JDetailed
description of
input functions
F Run/Reset
Reset Run
F Auto/Manual
F Hold/Hold cancel
F Advance
Advance
F Pattern select
Parameters

Table of Contents

Other manuals for Omron E5CK

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5CK and is the answer not in the manual?

Omron E5CK Specifications

General IconGeneral
Ambient Operating Temperature-10 to 55°C
Protection RatingIP20
Control TypePID
Input TypeThermocouple, RTD
Output TypeRelay, Voltage, Current
Power Supply Voltage100 to 240 VAC
Mounting TypePanel
Display TypeDigital
Control OutputRelay, Voltage, Current
Alarm OutputRelay
Dimensions48 x 48 x 78 mm
Ambient Operating Humidity25% to 85% RH

Related product manuals