CHAPTER 5 PARAMETERS
E5CK
5–6
Ă• The parameters in this mode can be used only when the security" parameter (proĆ
tect mode) is set to 0" to 5". Only the PV/Present SP" parameter can be used when
the security" parameter is set to 6".
Ă• The parameters in this mode comprise step operation parameters and parameters
required for monitoring program operating states.
Ă• To select this mode, press the
key for 1 second minimum. The display changes
to the menu display. If you select [
] then press the key for 1 second miniĆ
mum, the controller enters the level 0 mode.
Ă• To select parameters in this mode, press the key. To change parameter settings,
use the
or keys.
Ă• The following table shows the parameters supported in the level 0 mode and the page
where the parameter is described.
Symbol Parameter Name
Page
PV/Present SP 5-6
Pattern No. 5-7
Step No. monitor 5-7
Hold 5-8
Advance 5-8
Standby time monitor 5-9
Pattern elapsing time 5-9
Pattern execution count monitor 5-9
MV monitor (heat) 5-10
MV monitor (cool) 5-10
PV/Present SP
Ă• The process value is displayed on the No.1 display, and the Present SP is displayed
on the No.2 display.
Ă• The decimal point position is dependent on the selected sensor during temperatures
input and on the results of scaling during analog input.
Monitor Range
Unit
Process Value
Scaling lower limit -10%FS to scaling upper limit +10%FS
EU
Present SP
Set point lower limit to set point upper limit
EU
Ă• During temperature input, the range of the currently selected sensor is taken as the
PV monitor range.
ĂRelated parameters
Input type" Scaling upper limit" Scaling lower limit" Decimal point" (setup mode)
Set point upper limit" Set point lower limit" (expansion mode)
Level 0 Mode
Function
Monitor
See